Warning 
 Please read this instruction carefully before use. 
Switch off the power before wiring. 
The display panel of TP05G and TP08G is waterproof. But please prevent grease, corrosive liquids and sharp 
objects from contacting the TP05G and TP08G. 
The TP05G and TP08G require 24VDC input power. DO NOT connect input AC power supply to any of the RS-485 
communication port; otherwise serious damage may occur. Check all the wiring again before switching on the 
power. 
DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after the 
power is switched off. 
Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference. 
Please use the fixed support accessory which is packed together with the product provided by Delta. DO NOT 
tighten the screws out of the normal torque specifications; otherwise serious damage may occur. 
 Introduction 
 Explanation & Peripherals 
Thank you for choosing Delta TP Series. TP05G (BS2/BT2) has the features of high resolution 160×80 dots. 
When the font is Traditional Chinese character and the font size is 8, TP05G (BS2/BT2) is able to display 14×7 
Chinese character; TP08G (BS2/BT2) has the features of high resolution 240×128 dots. When the font is 
Traditional Chinese character and the font size is 8, TP08G (BS2/BT2) is able to display 21×11 Chinese 
character. Both of them provide multilingual display and two built-in communication ports, one is for RS-232 and 
the other is for RS-485/RS-422. RS-232 and RS-485 can be used simultaneously. Besides, they also support 
built-in RTC, communication/alarm indication LED, etc. functions. Besides, the users can purchase program 
copy card (optional) to copy settings and programs quickly and save download time. Regarding the editing 
software, there are various objects and images for various users’ requirements. Please ensure to use TP series 
with Delta power supply module, DVPPS01 and DVPPS02. 
 Product Outline 
Power LE D Indicator 
Al ar m LED Indicat or
Di splay Area
Function K eys
Escape/E xi t Key
Ar row K eys
Numeric K eys
Enter Key
Multi pl e Function Keys
 
 Function Specifications 
Model 
Specifications 
TP05G (BS2/BT2) 
TP08G (BS2/BT2) 
Screen Type / Display 
Color 
STN-LCD / Monochromatic 
Case Color 
BS2: White color, BT2: Black color 
Backlight 
The back-light automatic turn off time is 1~99 minutes (0 = do not turn off) 
(The back-light life is about 50 thousand hours at 25°C)   
Resolution 
160×80 dots 
240×128 dots 
Display Range 
83mm(W)× 41mm(H);   
3.8” (diagonal preferred) 
78mm(W)× 41mm(H);   
3.8” (diagonal preferred) 
Contrast Adjustment 
10 levels of adjustment 
Language/Font 
ASCII: (Code page 850) Alphanumeric (including European characters) 
Taiwan: (Big 5 codes) Traditional Chinese Fonts 
China: (GB2324-80 codes) Simplified Chinese Fonts 
5 × 8 dots 
32 characters × 10 rows 
48 characters × 16 rows 
8 × 8 dots 
20 characters × 10 rows 
30 characters × 16 rows 
8 × 12 dots 
20 characters × 6 rows 
30 characters × 10 rows 
Display Text 
8 × 16 dots 
20 characters × 5 rows 
30 characters × 8 rows 
ENGLISH 
Model 
Specifications 
TP05G (BS2/BT2) 
TP08G (BS2/BT2) 
Font Size 
ASCII: 5×8, 8×8, 8×12, 8×16 
Alarm LED Indicator (RED) 
1.  Power on indication (Blink for three times) 
2.  Communication error alarm 
3.  Special indication by user programming 
Program Memory 
1024KB flash memory 
Serial Communication Port 
RS-232(COM1) 
Unsynchronized transmission method: RS-232 
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits 
Parity: None/Odd/Even, Transmission speed: 9,600bps~115,200bps 
RS-232: 9 PIN D-SUB male 
Extension Communication 
Port 
RS-422(COM1) 
RS-485(COM2) 
Unsynchronized transmission method: RS-485 / RS-422 
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits 
Parity: None/Odd/Even, Transmission speed: 9,600bps~115,200bps 
RS-422: 9 PIN D-SUB male, RS-485: 6-Pin removal terminal 
Battery Cover 
DC 3V battery for HMI 
Extension Interface 
1.  Update firmware version   
2.  The slot for program copy card   
6-Pin Removal Terminal 
Include DC 24V input and RS-485 communication input 
 Electrical Specifications 
Model 
Specifications 
TP05G (BS2/BT2) 
TP08G (BS2/BT2) 
Display 
Monochromatic STN LCD 
Effective Display Area 
83mm(W)× 41mm(H); 3.8” (diagonal 
preferred) 
78mm(W)× 41mm(H); 3.8” (diagonal 
preferred) 
Display Resolution 
160×80 
5×8 dots  32 characters × 10 rows 
8×8 dots  20 characters × 10 rows 
8×12 dots  20 characters × 6 rows 
8×16 dots  10 characters × 5 rows 
240×128 
5×8 dots  48 characters × 16 rows 
8×8 dots  30 characters × 16 rows 
8×12 dots 30 characters × 10 rows 
8×16 dots 30 characters × 10 rows 
LCD Contrast Adjustment 
Set by Software, adjust the contrast by the press button in the function table 
LCD Backlight Type 
LED Backlight: Automatic Turn-off Setting 
Function / Numeric Keys 
0~9,F1~F5, ESC, ± , CLR, ←, 
‧,SHIFT, ENTER and Arrow Keys (UP, DOWN ) 
External Input Power 
24V (1.8W Max.) 
Memory Capacity 
1024K Byte 
CPU 
ST STR710RZT6 
RAM of System 
64K Byte 
Communication Interface 
COM1: RS-232/RS-422    COM2: RS-485 
Waterproof Class of Front 
Panel 
IP66 / NEMA4 / UL Type4 indoor 
Operating Temperature 
for Hardware 
0~50°C; 20-90% RH (non-condensing) 
Storage Temperature for 
Hardware 
-20~60°C 
Vibration 
5Hz
≦f<9Hz = Continuous: 1.75mm / Occasional: 3.5mm   
9Hz
≦f≦150Hz = Continuous: 0.5g / Occasional: 1.0g 
Shock 
15g peak, 11ms duration, half-sine, three shocks in each direction per axis,   
on 3 mutually perpendicular axes (total of 18 shocks) 
Radiated Emission 
CISPR11, Class A 
Electrostatic Discharge 
Immunity   
EN61000-4-2 
Radiated Immunity   
EN61000-4-3 
Electrical Fast Transient   
EN61000-4-4 
Weight / Dimensions 
0.43kg;    210×122×45mm (Width(W) × Height(H) × Deep(D)) 
Cooling Method 
Natural Air Cooling 
 Dimension and Installation 
 Product Outlook and Dimensions (Units: mm, [ ]: inch) 
Back Panel 
 
6-Pin Terminals:   
Wire Gauge:12-24 AWG / Torque:4.5 lb.-inch 
Front Panel and Right Side Diagram   
210 [8.2677]
1
2
2
 [
4
.8
0
3
1
]
45 [1.7717]
1
0
8
.2
6
 [
4
.2
6
2
]
 
Mounting Dimensions (Panel Cutout) 
 
Vertical View 
196.26 [7.7266]
3
7
.5
 [
1
.4
7
6
4
]
7
.5
 [
0
.2
9
5
3
]
 
 Installation 
Please insert TP05G/TP08G to the opening hole of panel and tighten the screws. However, if a firm mounting 
TP05G/TP08G to the panel is needed, please use the mounting fixed support accessory which is packed 
together with TP05G/TP08G, then insert the fixed support in the back and tighten the screws. Please refer to 
the following sections for correct installation. (   If the fixed support is not installed well, Delta will not 
guarantee the waterproof function. The screw torque should be 4-5(kg-cm). DO NOT exceed this specification 
when tightening the screws; otherwise TP05G/TP08G may be damaged.) 
 
Do not install and mount TP05G/TP08G in the following environment.   
 A location subjected to Airborne dust, metallic particles, oil and smoke, corrosive or flammable 
gases and liquids. 
 A location where temperature and humidity will exceed specifications.   
 A location where vibration and shock will exceed specifications. 
The flat surface should be a UL Type 4 
“Indoor Use Only” enclosure or equivalent (IP66/NEMA4). Please 
refer to the figures below. 
 
 
Installation Method of Insert Module 
 
 
 Password Function 
If the users forgot the password, the password can be cleared by using the following code: 
8888
. This 
universal code will clear the password and all TP05G/TP08G internal programs. The TP05G/TP08G will be 
reset to the factory settings. Please pay close attention when using it. The password can be the alphabet from 
A to Z or the number from 0 to 9. But it must use the function keys F0~F5 to input the password characters. 
Please refer to the following table.   
Function Key 
Use Method 
Function Key 
Use Method 
Numeric Key  0 ~ 9 
F3 
Scrolls in a loop as follows 
J→K→L→M→N→O→P→Q→R 
F1 
This key is left direction key and it can 
be used to select the position of the 
value.   
F4 
Scrolls in a loop as follows 
S→T→U→V→W→X→Y→Z 
F2 
Scrolls in a loop as follows 
A→B→C→D→E→F→G→H→I   
F5 
It can be a right direction key in the 
system menu. 
 Hardware Operation 
When the users want to startup TP05G/TP08G, a 24VDC power is needed. After applying 24VDC power to 
TP05G/TP08G, it will enter into the startup display and then enter the user-designed program. Pressing Esc 
key and holding on for 5 seconds can return to system menu. There are five selections in the system menu 
and are described below. 
SELECTIONS 
EXPLANAION 
Download 
Program 
Use the connection cable (DVPACAB530) to connect the TP05G/TP08G serial communication 
port RS-232 to a PC. Then use the TPEditor software to download an application program to 
TP05G/TP08G. 
Upload Program 
Use the connection cable (DVPACAB530) to connect the TP05G/TP08G serial communication 
port RS-232 to a PC. Then use the TPEditor software to upload an application program from 
TP05G/TP08G.   
Copy Program 
Transfer a program between two TP05G/TP08G units. 
1: Transmit Program ; 2: Receive Program 
When transmit programs and data between two TP05G/TP08G units. Set one TP05G/TP08G to 
“Receive Program” mode and the other TP05G/TP08G to “Transmit Program” mode. Please use 
twisted pair wires to connect the two units via the RS-485 ports. 
TP05G/TP08G 
Settings 
There are 8 items that used to modify TP05G/TP08G system settings: 
1. Communication protocol: Setting the address of TP05G/TP08G, and the communication 
string for either RS-232 or RS-485. 
2. Contrast: Adjust the contrast of LCM display screen. 
3. Back-light: adjust the automatic turn off time of LCM. Setting range is 00~99 seconds. If set 
to 00, the LCM Back-light will not turn off. 
4. Date and Time: It is used to set the TP05G/TP08G built-in RTC including year, month, day, 
hour, minute, second and week. Also the internal battery capacity display is shown here. 
5. Buzzer: Used to set the buzzer sound, normal mode or quiet mode. 
6. Language Setting: Used to set the displayed language. English, Traditional Chinese, 
Simplified Chinese or user-defined language. 
7. Password setting: Used to set, enable, and disable the password function. If the password 
function is enabled, it will require the user to input a password before entering any system 
menu. The factory password is 
1234
8. Startup Display: Used to select the TP05G/TP08G startup display. User can select “user 
defined” to use the file that designed by TPEditor software and download to TP05G/TP08G. 
PLC Connection 
There are three methods to connect to PLC: 
1. Using TP05G/TP08G serial communication port (COM1) RS-232: set 8-pin DIP switch to 
RS-485 mode and connect the cable (DVPACAB215 or DVPACAB230) to program 
communication I/O RS-232C of PLC. 
PLC Connection 
2. Using extension communication port (COM2): set 8-pin DIP switch to RS-485 mode and 
connect 5-pin removal terminal of extension communication port to RS-485 of PLC with 
twisted pair. 
3. Using extension communication port (COM1): set 8-pin DIP switch to RS-422 mode and 
connect four pins (6, 7, 8, 9) of 9 PIN D-SUB male to RS-422 of PLC with 4-wire cable. 
Execution 
Execute the internal program that download from TPEditor software or transmitted from other 
TP05G/TP08G units. When program is in execution, the user can return to system menu by 
pressing Escape/Exit (Esc) key for 5 seconds.   
 Communication Connection 
TP05/08G may connect to a PC by using connection able DVPACAB515 
PC or TP05/08G
1
5
6
9
9 PIN D-SUB
TO PC (RS-232)
TO TP05/08G
5
1
9
6
9 PIN D- SU B
 
9  PIN D-SUB female
R x 
2
GND     5
5       GND
PC  COM Po rt
9  PIN D-SUB fe ma le
T x
R x
TP05/0 8G COM Port
Tx 
3
 
TP05/08G may connect to a DVP-PLC by using connection cable DVPACAB215/ DVPACAB230 / 
DVPACAB2A30 
1. DVPACAB215
/DVPACAB230 
TO  PC or TP05/08G 
1
13
14
1
5
6
9
25 PIN D-SUB
9 PIN D-SUB
TO PLC
MINI DIN TERMINAL 
 
2. DVPACAB2A30 
TO  PC or TP05/08G 
1
5
6
9
9 PIN D-SUB
TO PLC
MINI DIN TERMINAL 
 
8 PIN MINI DIN
25 PIN D-SUB female
PC/TP COM Port
PLC CO M1 Port
Tx 
2
GND
7
 
8 PIN MINI DIN
9  PIN D-SUB female
PC/TP COM Port
PLC CO M1 Port
4       Rx 
8       G ND
Rx 
2
GND    5
1,2    5V
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
4       Rx 
8       G ND
1,2    5V
6
8
20
4
5
1
4
6
7
8
5       Tx
Rx       3
Tx       3
 
 
5       Tx 
 
TP05G/08G  The Pin definition of 9 PIN D-SUB 
1. RS-232 
3       Tx 
5       GND
RS-232  9  PIN D-SUB male
TP05/08G COM Port
2       Rx 
 
2. RS-422 
8       Tx +
RS-422  9  PIN D-SUB male
9       Tx -
TP05/08G COM Port
7       Rx -
6       Rx +
 
3. DVPACAB630 (RS-422) 
TO  TP05/08G 
1
5
6
9
9 PIN D-SUB
TO PLC
MINI DIN TERMINAL 
 
 
8 PIN MINI DIN
9  PIN D-SUB female
TP05/08G COM Port
MITSUBISHI  FX-PLC 
Rx - 
7
Tx+      8
1
2
3
4
5
6
7
8
7       Tx+ 
2       Rx+
Tx -      9
3       SG
GND    5
Rx+ 
COM1 Port RS-422
6
4       Tx - 
1       Rx -
 
Switch between RS-422 / RS-485 (by using 8-PIN DIP switch) 
8-PIN DIP switch 
RS-485 
RS-422 
SW1 ~ SW4 
On 
Off 
SW5 ~ SW8 
Off 
On 
 Battery Life and Precision of Calendar 
  Timer 
Battery Life 
 
 
 
Precision of Calendar Timer 
1. At 0°C/32°F, less than -117 seconds error per month.   
2. At 25°C/77°F, less than 52 seconds error per month. 
3. At 55°C/131°F, less than -132 seconds error per month. 
 
Temperature (°C) 
-20 
20 
60 
Life (Year) 
1.972 
2.466 
2.712 
2.835 
 
注意事項 
  請在使用之前,詳細閱讀本使用說明書。 
  實施配線,務必關閉電源。 
  本機顯示操作面板防水,但對油污或具腐蝕性之液體不具防護作用,避免以尖銳之物品刮傷面板使用時請注
意。 
  本機輸入電源為直流 24V,不可連接於 RS-485 通訊口信號端,否則可能造成嚴重的損壞,因此請在上電之前
再次確認電源配線。 
  輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。請勿在上電時觸摸任何端子。 
  本體上之接地端子   務必正確的接地,可提高產品抗雜訊能力。 
  利用原廠包裝附件之固定架,鎖緊面板固定螺絲時,請勿太緊以免造成機殼損壞。 
 
產品簡介 
  說明及週邊裝置    
謝謝您採用台達文本顯示器系列產品。TP05G (BS2/BT2)  為解析度  160×80,當字體為新細明體字體大小 8 時,
可顯示 14×7  個中文字的文本顯示器;TP08G  (BS2/BT2)  為解析度  240×128,當字體為新細明體字體大小 8
時,可顯示 21×11  個中文字的文本顯示器。兩者皆支援多國文字顯示,以及內建兩個通訊口(RS-232 及  RS-485
/RS-422  ,其中 RS-232 與 RS-485 可同時使用)。並內建萬年曆、通訊/警告指示  LED 等功能。使用者可另
購外接程式複製單元,快速移植程式,節省程式下載時間。軟體規劃部份更提供多種物件圖形可供使用者選用。
請搭配台達 DVPPS01,DVPPS02(電源模組)一起使用。 
 
產品外觀及各部介紹 
顯示區
功能鍵
警示指示燈
電源指示燈
退出/取消鍵
命令操作鍵
數值鍵
輸入鍵
複合功能鍵
 
 
功能規格 
 
功能規格 
機型 
規格 
TP05G (BS2/BT2) 
TP08G (BS2/BT2) 
/
彩 
STN-LCD / 
單色 
色 
BS2
:白色,BT2:黑色 
光 
背光自動關閉設定範圍 1 ~ 99 分鐘(設定值 0 為不關閉) 
(在常溫 25℃下壽命約 5 萬小時) 
度 
160
×80  點 
240
×128  點 
圍 
(W)×(H)= 83×41(單位:mm); 
3.8
吋(對角線) 
(W)×(H)= 78×41(單位:mm); 
3.8
吋(對角線) 
調
整 
10
段明暗調整 
型 
ASCII
:(頁碼 850)文字(包含歐洲字型) 
台灣:(BIG 5 碼)繁體字型 
中國:(GB2324-80 碼)簡體字型 
5
×8  畫素字型 
32
個字×10 列 
48
個字×16 列 
8
×8  畫素字型 
20
個字×10 列 
30
個字×16 列 
8
×12  畫素字型 
20
個字×6 列 
30
個字×10 列 
顯示的 
文字數 
8
×16  畫素字型 
20
個字×5 列 
30
個字×8 列 
繁體中文 
小 
ASCII
:5×8,8×8,8×12,8×16 
警 示 指 示 燈 ( 紅 燈 ) 
電源啟動指示(亮/滅三次)/通訊不通警示/使用者程式指定 
憶 
1024KB
快閃記憶體 
埠 
R S - 2 3 2
( C O M 1 ) 
非同步傳送方式:RS-232 
資料長度:7 或 8 個位元,停止位元:1 或 2 個位元 
極性:None/Odd/Even,傳送速度:9,600bps ~ 115,200bps 
RS-232
:9 PIN D-SUB male 
埠 
R S - 4 2 2
( C O M 1 ) 
R S - 4 8 5
( C O M 2 ) 
非同步傳送方式:RS-485/RS-422 
資料長度:7 或 8 個位元,停止位元:1 或 2 個位元 
極性:None/Odd/Even,傳送速度:9,600bps ~ 115,200bps 
RS-422
:9 PIN D-SUB male 
RS-485
:6Pin 脫落式端子 
蓋 
可由此更換人機直流 3V 電池 
面 
更新韌體版本、程式複製卡插槽 
6 P i n
脫 落 式 端 子 
包含直流電源 24V 輸入及 RS-485 通訊輸入 
 
電氣規格 
機型 
項目 
TP05G (BS2/BT2) 
TP08G (BS2/BT2) 
器 
單色  STN LCD 
積 
(W)×(H)= 83×41(單位:mm); 
3.8
吋 
(W)×(H)= 78×41(單位:mm); 
3.8
吋 
度  160×80 
5
×8 
8
×8 
8
×12 
8
×16 
英文字 
英文字 
英文字 
英文字 
32
×10 字 
20
×10 字 
20
×6  字 
10
×5  字 
240
×128 
5
×8 
8
×8 
8
×12 
8
×16 
英文字 
英文字 
英文字 
英文字 
48
×16 字 
30
×16 字 
30
×10 字 
30
×8 字 
L C D
對 比 調 整 
軟體設定,使用功能表內按鍵調整 
L C D
背 燈 型 式 
LED
背燈:自動關閉設定 
功 能 鍵 / 數 字 鍵  0 ~ 9,F1 ~ F5,ESC,±,CLR,←,‧,SHIFT,ENTER 及方向鍵(UP,  DOWN) 
源 
24V
(1.8W Max.) 
量 
1024K Byte 
中央處理單元 (CPU) 
ST STR710RZT6 
R
A
64K Byte 
面 
COM1
:RS-232/RS-422    COM2:RS-485 
前 面 板 防 水 等 級 
IP66
/NEMA4/UL Type4 indoor 
硬 體 使 用 溫 度 
0 ~ 50
℃;相對濕度 20 - 90﹪RH(不可凝結) 
硬 體 儲 藏 溫 度 
-20 ~ 60
℃ 
動 
 
5Hz
≦f<9Hz 
連續:1.75mm/非連續:3.5mm 
 
9Hz
≦f≦150Hz  連續:0.5g/非連續:1.0g 
擊 
15g peak
,11ms,半弦波,X, Y, Z 軸正負各 3 次,共 18 次 
R
F
輻 射 測 試 
CISPR11
,Class A 
靜 電 放 電 測 試 
EN61000-4-2 
耐 R F 輻 射 度 測 試 
EN61000-4-3 
高 頻 暫 態 測 試 
EN61000-4-4 
重 量 / 外 型 尺 寸 
0.43kg
;210×122×45mm(寬(W)×  高(H)×  厚(D)) 
式 
空氣對流自然冷卻