ADAM-5000 I/O Modbus Mapping Table
 
 
G-8 ADAM 5000 Series User’s Manual
 
 
G.5 Address mapping of ADAM-5080 For ADAM-5000 
ModBus 
 
Slot Start Address :S(word) 
 
OFFSET 
bit 
 
 HIGH 
BYTE 
LOW 
BYTE 
 
 
 
 
S+0 
CH0 
S+1 
CH0 counter value (Long Word) 
S+2 
CH1 
S+3 
CH1 counter value(Long Word) 
S+4 
CH2 
S+5 
CH2 counter value(Long Word) 
S+6 
CH3 
S+7 
CH3 counter value(Long Word) 
15 14 13 12 11 10  9  8  7  6  5  4 3 
CH0 
Status 
flg 
 
 
 
S+8 
reserve 
Bit 0 :Counter start/stop 
Bit 1:Counter Reset 
Bit 2 :Counter Over Flow Flag 
CH1 
Status 
flg 
 
 
 
S+9 
As Above 
As Above 
CH2 
Status 
flg 
 
 
 
S+10 
As Above 
As Above 
CH3 
Status 
flg 
 
 
 
S+11 
As Above 
As Above 
 S+12~ 
S+15 
RESERVE 
 
Nots: 
1
st
 bit: Default ON “1”, available to set ON/OFF to start/stop counting. 
2
nd
 bit: Normal OFF “0”, only accept a pulse ON signal to clear the 
counter and only available when 1
st
 bit is OFF. 
3
rd
 bit: Normal OFF “0”, only turning ON “1” when counter overflow. 
Users can write “0”to clear the overflow flag.  tuig 
 