 Unit Installation
61200860L1-34AB
Copyright © 2012 ADTRAN, Inc.
73
Instructions for Connecting DC Power Source to the NetVanta 3205
Step
Action
For +24 VDC operation:
1
Connect the negative terminal of the +24 VDC power source to the negative terminal of the NetVanta 
3205 DC power connector located on the rear of the unit. (See 
.)
2
Connect the negative terminal of the +24 VDC power source to the chassis ground of the +24 VDC power 
source.
or
Connect the negative terminal of the +24 VDC power source to Earth ground.
3
Connect the positive terminal of the +24 VDC power source to the positive terminal of the NetVanta 3205 
DC power connector.
4
Connect the ground terminal of the NetVanta 3205 DC power connector to Earth ground. 
For -48 VDC operation:
1
Connect the positive terminal of the -48 VDC power source to the positive terminal of the NetVanta 3205 
DC power connector located on the rear of the unit. (See 
.)
2
Connect the positive terminal of the -48 VDC power source to the chassis ground of the 
-48 VDC power source.
or
Connect the positive terminal of the -48 VDC power source to Earth ground.
3
Connect the negative terminal of the -48 VDC power source to the negative terminal of the NetVanta 3205 
DC power connector.
4
Connect the ground terminal of the NetVanta 3205 DC power connector to Earth ground.