Siemens CP 243-2 User Manual

Page of 150
Command Interface
5-17
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
5.2.5
Store_Actual_Parameters
Purpose
This call overwrites the permanently stored configured parameters with the actual
parameters, in other words the parameters are reconfigured.
For AS-i slaves that comply with the AS-i slave standard profile 7.4, the AS-i
master manages the AS-i slave parameter assignment itself. The configured
parameters for these AS-i slaves always have the value F
 
H
.
Structure of the Job Data in the Send Buffer
Bank
Byte
Meaning
2
0
Command number: 04 
H
Structure of the Job Data in the Receive Buffer
Bank
Byte
Meaning
2
0
Echo of the command number: 04 
H
2
1
Command status