5.2.13
Set_Operation_Mode
Purpose of the Command
With this call, you can select between the configuration mode and the protected
mode.
mode.
In the protected mode, only AS-i slaves are activated that are entered in the LPS
and whose expected and actual configurations match, in other words when the I/O
configuration and ID codes of the detected AS-i slaves are identical to the
configured values.
and whose expected and actual configurations match, in other words when the I/O
configuration and ID codes of the detected AS-i slaves are identical to the
configured values.
In the configuration mode, all detected AS-i slaves (except for slave address “0”)
are activated. This also applies to AS-i slaves in which there are differences
between the expected and actual configuration.
are activated. This also applies to AS-i slaves in which there are differences
between the expected and actual configuration.
The “OPERATION MODE” bit is saved permanently in the EEPROM, i.e. it is
retained following a startup/restart.
retained following a startup/restart.
When changing from the configuration mode to the protected mode, the CP 243-2
is restarted (transition to the offline phase followed by switchover to the online
mode).
is restarted (transition to the offline phase followed by switchover to the online
mode).
Note
If an AS-i slave with the address “0” is connected, the CP 243-2 cannot switch
from the configuration mode to the protected mode.
from the configuration mode to the protected mode.
Structure of the Job Data in the Send Buffer
Bank
Byte
Meaning
2
0
Command number: 0C
H
2
1
Operating mode
protected mode: 00H
configuration mode: 01H
Structure of the Job Data in the Receive Buffer
Bank
Byte
Meaning
2
0
Echo of the command number: 0C
H
2
1
Command status