Siemens SIMATIC NET PROFIBUS User Manual

Page of 490
17
Version 1.0 8/00
4 Setting Up
4.3 Setting compatibility, operating mode and transmitting power 
4.3 Setting compatibility, operating mode and transmitting power
Please note:
The OLM must be switched off when changing the operating mode.
You can switch off the OLM by, e.g., unplugging the 5-pin terminal block.
4.3.1 Setting the compatibility 
The DIL switch S7 is used to switch the functional compatibility to devices of the preceding generation (SINEC L2FO
OLM/P3, -P4, -S3, -S4, S3-1300 and -S4-1300) either off or on. Default setting at S7 is Position 0 (compatibility is
switched off).
DIL switch S7 (compatibility) in Position 0:
compatibility 
to SINEC L2FO OLM/P3, -P4, -S3, -S4, -S3-1300, -S4-1300 switched off
DIL switch S7 (compatibility) in Position 1:
compatibility 
to SINEC L2FO OLM/P3, -P4, -S3, -S4, -S3-1300, -S4-1300 switched on
The functional compatibility to SINEC L2 Optical Link Modules of the preceding generation SINEC L2FO OLM/P3,
OLM/P4, OLM/S3, OLM/S4, OLM/S3-1300 and OLM/S4-1300 is switched on with the DIL switch S7=1
This operating mode is required when operating this module together with new devices. 
Only turn switch S7 to Position 1 if the PROFIBUS OLM is being used as a spare or expansion device in existing
networks in conjunction with OLMs of the preceding generation, and a direct optical connection is to be made.
The following illustrations show the switch assignment of the OLM at S7=1 for
Further information about adjusting the S7 in Position 1
can be found in the ”Description and Operating
Instructions SINEC L2 Optical Link Module OLM/P …,
OLM/S …“ for this SINEC L2 OLM.
SINEC L2FO
OLM/S3; OLM/S4;
OLM/S3-1300; OLM/S4-1300
OLM/S3, OLM/S3-1300: 
S2 reserved
OLM/S3, OLM/S4, 
OLM/S3-1300 und 
OLM/S4-1300:
SINEC L2FO
OLM/P3; OLM/P4
OLM/P3 und OLM/P4:
OLM/P3: S6 reserved
S7 = 1 Compatibility Mode ON
S0
Reserved
S3,S4
Reserved
S1
Mode
Monitor
0
Line/Ring
On
1
Line
Off
0
Off
1
On
S2
Redundancy
S7 = 1 Compatibility Mode ON
S0
Reserved
S1
Mode
Monitor
0
Line/Ring
On
1
Line
Off
0
Off
1
On
S2
Redundancy
S5
Output Power CH3
0
Standard
1
High
0
Standard
1
High
S6
Output Power CH4
S3
Distance
0
Extended
1
Standard
S4,S5,S6
Reserved
0
1
S 6
S 7
S 1
S 2
S 4
S 5
S 3
S 0
0
1
S 6
S 7
S 1
S 2
S 4
S 5
S 3
S 0