For a 208Y/120V three-phase wye panel with the 120V variant of the
meter:
meter:
•
Connect meter terminal A to the voltage disconnect phase A (red wire)
•
Connect meter terminal B to the voltage disconnect phase B (black
wire)
wire)
•
Connect meter terminal C to the voltage disconnect phase C (blue wire)
•
Connect meter neutral terminal to neutral bar in the voltage disconnect
panel (white wire)
panel (white wire)
•
Connect earth wire to earth post using lug provided
•
Install power supply shorting jumpers (see Figure 7)
Figure 7: PowerLogic EM4800 meter 208Y/120V three-phase wye
service connection
service connection
Legend:
1 BX cable
2 Earth
3 Phase C (blue)
4 Phase B (black)
5 Shorting jumper
6 Sense voltage terminal block (J3)
7 Neutral (white)
8 Phase A (red)
9 0.75-inch (1.9-cm) strain relief
1 BX cable
2 Earth
3 Phase C (blue)
4 Phase B (black)
5 Shorting jumper
6 Sense voltage terminal block (J3)
7 Neutral (white)
8 Phase A (red)
9 0.75-inch (1.9-cm) strain relief