Schneider Electric 17S Series User Manual

Page of 146
91
Electrical Specifications - Power, continued
Internal Power 
Dissipation 
Specifications 
Table
The following table provides 17S internal power dissipation at maximum continuous 
output power. This information may be useful to size the thermal capability of the 
mounting cabinet.
Note: These power dissipations are measured at maximum continuous power and 
should be considered worst case. Often in sizing servo systems, factors such as 
profile duty cycle may reduce these numbers. These values do not include power 
dissipated in the Regen resistor. This is application-specific and must be calculated 
separately.
Quiescent dissipation when output stage is disabled is 15 W
Model Number
Power
MHDS1004N00
30 W 
MHDS1008N00
40 W
MHDS1017N00
60 W
MHDS1028N00
90 W
MHDS1056N00
200 W