Error Messages
Error 
Identification 
and Description
Errors are generated when a fatal fault occurs. Fatal faults cause the drive to be 
disabled, the brake (if installed) to be activated and the fault relay contacts to open. 
Either of the programmable digital outputs can also be programmed to indicate that 
an error has been detected. The cause of the error is presented as an 
alphanumeric code on the drive’s front panel LED display; these error codes are 
identified and described in the following table.
Continued on next page
Error 
Code
Error (Fault)
Possible Cause/Corrective Action
F01 
Drive heat sink 
overtemperature. 
- Improve ventilation.
- Reduce motion profile duty cycle.
F02
DC link voltage limit 
exceeded.
- Check Parameter “Mains Supply Voltage” for correct
   setting.
- Supply voltage too high; use a mains transformer.
- Regen power limit was exceeded; adjust motion
  profile or install larger regen resistor.
F03
Following error limit 
exceeded.
- Increase I
rms
 or I
peak
 (keep within motor operating
  range).
- SW ramp parameters set too large.
F04
Feedback signals missing 
or incorrect.
- Defective feedback device.
- Check  for correct device type selected in “Feedback
  Type” parameter.
- Check feedback cable and connections.
F05
DC-link voltage less then 
factory preset (100V).
Supply voltage not present or too low when drive was 
enabled.  Only enable the drive when the mains supply 
voltage has been on longer than 500 ms.