APC 6000 User Manual
6739389EN/FB
- Page 31
System information
(continued)
Battery and adjustments
fields
fields
Legend:
◗
no entry: not available;
◗
yes: available in this cubicle;
◗
bat: available in this cubicle if
battery installed;
◗
bat/opt: available if option
installed.
Inverter type:
◗
0: unitary;
◗
1: parallel without static switch;
◗
2: parallel with static switch;
◗
3: Static Switch cubicle.
Battery installed:
◗
0 = no;
◗
1 = yes.
Sensor installed:
◗
0 = no;
◗
1 = yes.
battery measurements
units
JBUS address type
hex. word
hex. word
unitary
parallel
SS
U battery
V
1C0
yes
yes
I battery
A
1C1
bat
bat
battery backup time
mn
1C2
bat/opt
bat/opt
battery room temperature
°C
1C3
bat/opt
bat/opt
battery adjustments
units
JBUS address type
hex. word
unitary
parallel
SS
inverter type
-
200
yes
yes
yes
battery installed
-
201
yes
yes
battery temperat. sensor
-
202
yes
yes
In (I rated load)
A
208
yes
yes
yes
Pn (P rated load)
kW
209
yes
yes
yes
rectifier-charger
bit meaning
JBUS
type
information
address
hex.
hex.
bit=0
bit=1
bit
word unit. para. SS
B_Etat_QF1
open
closed
400 40
bat
bat
B_Etat_Dech_Bat
not discharging discharging
401
bat
bat
B_Etat_Ubat_Min
not reached
min. volt. fault
402
bat
bat
B_Etat_Ubat_Aut
not reached
warning
403
bat
bat
B_Etat_Tempe_Ht
normal
outside toleran. 404
bat
bat
B_Etat_Res1_Ht
not reached
outside toleran. 405
bat
bat
B_Etat_Vent_Bat
no fault
fault
406
yes
yes
B_Etat_Cha_Bat
not charging
charging
407
bat
bat
B_Etat_Pont
off
on
408
bat
bat
B_Etat_Def_Maj_Cha no fault
fault
409
yes
yes
B_Etat_Q1
open
closed
40E
yes
yes
B_Etat_Arr_Urg
not activated
activated
411 41
yes
yes
B_Etat_U_Res1
normal
outside toleran. 412
yes
yes
B_Etat_F_Res1
normal
outside toleran. 413
yes
yes
B_Etat_Arr_Prog
not activated
activated
417
bat
bat
B_Etat_Lim_Groupe
not activated
activated
419
bat
bat
B_Etat_IBat_Aux
not activated
activated
41A
bat
bat
B_Etat_Egal_Bat
not active
active
41B
bat
bat
B_Etat_Groupe
not activated
activated
41E
yes
yes
Tables of binary data
Rectifier-charger
Legend:
◗
no entry: not available;
◗
yes: available in this cubicle;
◗
bat: available in this cubicle if
battery installed.