Installing the NetAXS-123 Panels
System Configuration
NetAXS-123 Access Control Unit  Installation GuideDocument 800-05779, Revision A
53
Figure 17:    RS-485 Connection via PCI-3 with Multidrop Panels at Both Ends
Note:  
You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an 
Earth Ground.
COM Port
See RS-485
Cable Note
EG
EG
Only Earth Ground (EG) 
one side of cable
RS-485 (4,000 Ft.)
RS-232 (50 Ft. Max.)
EG
EG
Only Earth Ground (EG) 
one side of cable
EG
PCI3
DIP Switch Settings
S1-S5 Panel Address
S6: OFF 
S7: OFF
S8-S9: OFF: 485 
Termination OFF 
DIP Switch Settings
S1-S5 Panel Address
S6: OFF 
S7: OFF
S8-S9: ON: 485 
Termination ON            
DIP Switch Settings
S1-S5 Panel Address
S6: OFF 
S7: OFF
S8-S9: OFF: 485 
Termination OFF 
DIP Switch Settings
S1-S5 Panel Address
S6: OFF 
S7: OFF
S8-S9: ON: 485 
Termination ON