4300 Series Ancillary Cabinets Installation and Operation Manual
Table 10.3 - 431A
 Input/Output Power Cable Sizes
(
Cable sizes for 75°C Copper Cable)
Recommended/Maximum Wire size and 
Torque Requirement
Trans
-
former
Code
Input/Output T
rans
-
former V
oltage
Xfmr T
ype
30 kV
A
50 kV
A
Tightening 
Torque
Phase A
WG*
Neutral A
WG*
Phase A
WG*
Neutral A
WG*
Input
B
208V
Δ
to
208/120V
Y
Input Iso
2 - 250 kcmil
N/A
2/0 - 250 kcmil
N/A
200 in.-lbs.
C
240V
Δ
to
208/120V
Y
Input Iso
3 - 250 kcmil
N/A
1/0 - 250 kcmil
N/A
200 in.-lbs.
N
380V
Δ
to
208/120V
Y
Input Iso
6 - 250 kcmil
N/A
3 - 250 kcmil
N/A
200 in.-lbs.
N
400/415V
Δ
to
208/120V
Y
Input Iso
6 - 250 kcmil
N/A
3 - 250 kcmil
N/A
200 in.-lbs. 
S
480V
Δ
to
208/120V
Y
Input Iso
6 - 250 kcmil
N/A
4 - 250 kcmil
N/A
200 in.-lbs.
M
600V
Δ
to
208/120V
Y
Input Iso
6 - 250 kcmil
N/A
6 - 250 kcmil
N/A
200 in.-lbs.
X
208/120V 
Y 4 wire input 
(No T
ransformer)
N/A
1/0 - 250 kcmil
4/0 - 350 kcmil
250 kcmil
350 kcmil
200 in.-lbs.
K
480/277V 
to 
208/120V 
Y
Input Auto
6 - 250 kcmil
3 - 350 kcmil
3 - 250 kcmil
2/0 - 350 kcmil
200 in.-lbs.
Output
F
208/120V 
Y 4 wire input 
(No T
ransformer)
N/A
1/0 - 250 kcmil
4/0 - 350 kcmil
250 kcmil
350 kcmil
200 in.-lbs.
H
208/120V 
to 
220/127V 
Y
Output Auto
1 - 250 kcmil
4/0 - 350 kcmil
4/0 - 250 kcmil
350 kcmil
200 in.-lbs.
J
208/120V 
to 
240/139V 
Y
Output Auto
2 - 250 kcmil
3/0 - 350 kcmil
3/0 - 250 kcmil
350 kcmil
200 in.-lbs.
P
208/120V 
to 
380/220V 
Y
Output Iso
4 - 250 kcmil
1 - 350 kcmil
1 - 250 kcmil
4/0 - 350 kcmil
200 in.-lbs.
Q
208/120V 
to 
400/230V 
Y
Output Iso
4 - 250 kcmil
1 - 350 kcmil
2 - 250 kcmil
3/0 - 250 kcmil
200 in.-lbs. 
K
208/120V 
to 
480/277V 
Y
Output Auto
6 - 250 kcmil
3 - 350 kcmil
3 - 250 kcmil
2/0 - 250 kcmil
200 in.-lbs.
M
208/120V 
to 
600/347V 
Y
Output Iso
6 - 250 kcmil
4 - 350 kcmil
4 - 250 kcmil
1/0 - 250 kcmil
200 in.-lbs.
 
* Wire capacity for Phase lugs is 250 kcmil - 6 
AWG, Neutral lugs is 350 kcmil - 6 
AWG.