Hardware Maintenance Manual: IBM PC Server/Enterprise Racks
 
 
6.
Install the 1U blank filler panel 
c1d on the front of the rack cabinet at the same U 
level as the Rack PDU.  Use two M6 screws that come with this option.
Proceed to “Cabling your PDUs” on page 148 for instructions on how to cable 
your Rack PDU.
Installing two devices horizontally
Use the following procedure to mount two Rack PDUs horizontally in your rack 
cabinet:
1.
Refer to the documentation that comes with your rack cabinet for additional 
information.
Notes:
a.
Removing the rack doors and side panels might make your Rack PDU 
installation easier.
b.
Use clip nuts for rack cabinets with round holes; use cage nuts for rack 
cabinets with square holes.
2.
Verify that the circuit breaker switch is in the Off position before installing your 
Rack PDU.
3.
Attach a dual-device attachment bracket 
c6d to the right side of one of the Rack 
PDUs with two M3x5 screws; then, attach another dual-device attachment bracket 
c5d to the left side of the other Rack PDU with two M3x5 screws.
Notes:
a.
When you install two Rack PDUs next to each other, you will need some parts 
from both options.
b.
Turn the second dual-device attachment bracket 
c5d so that the threaded 
holes are on the opposite side of the device as the holes on the other 
attachment bracket 
c6d.
Cage
nuts
Cage
nuts
Clip
nuts