Hardware Maintenance Manual: IBM PC Server/Enterprise Racks
 
 
Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950, CSA 
22.0-950, EN-60950, and IEC-950 standards.  The following table contains the product 
specifications for the Rack PDU:
Height
43 mm (1.7 in.)
Width
192 mm (7.5 in.)
Depth
221 mm (8.7 in.)
Weight
1.5 kg (3.2 lbs)
Operating temperatures
10
°
C–35
°
C (50
°
F–95
°
F) at 0–914 m (0–3000 ft)
10
°
C–32 
°
C (50
°
F–90
°
F
°
)
 
at 914–2133 m (3000–7000 ft)
Operating humidity
8–80% (non-condensing)
Rated voltage
100–240 V ac, 15 A, single-phase
Rated frequency
50–60 Hz
Maximum power rating
3600 VA
Circuit breaker
Two-pole, 15 A with time-delay protection for up to 600 A 
input current without nuisance tripping.
Power inlet
IEC 320-C20 inlet rated at 16 A (VDE) / 20 A (UL/CSA)
Power outlets
Seven IEC 320-C13 outlets rated at 10 A (VDE) / 15 A 