IBM PC Server/Enterprise rack enclosures
General checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Power checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Powering off the rack. . . . . . . . . . . . . . . . . . . . . . . . .  3
General checkout
Use the following procedure for diagnosing keyboard, mouse, and video problems for 
the IBM PC Server Rack Enclosure and the IBM Rack enclosures (Type 9306 and Type 
9308).
Attention:
For Models 4QS, 4QX, 9QS, 9QX, 9TS, 9TX only:
Ensure that the voltage selector switch on each server installed in the server rack 
is set to 230 V ac.
For Models 200, 900 only:
Ensure that the voltage selector switch on each server installed in the server rack 
is set to the proper voltage as supplied by the Power Distribution Unit, PDU.
1.
Check the following:
Ensure the external power cord is in good condition and properly connected 
to a known-good power source.
Ensure the internal power cables are in good condition and properly 
connected. (The internal power cables connect between the power 
distribution unit and the servers installed in the server rack.)
Ensure the following devices are powered on.
a.
Power distribution unit
b.
Server selector unit
c.
All system units
d. Display
2.
If the items/conditions specified in step 1. are not okay, correct the problem and 
verify that the server rack is operating correctly.
3.
If the items/conditions specified in step 1. are okay, then, using the server selector 
keypad buttons, check the operation of the failing device for all of the servers that 
are installed in the rack. 
4.
Did the failure occur on more than one server?
NO:
  Go to the Hardware Maintenance manual for the server that was 
selected when the failure occurred. Disconnect the keyboard and mouse from 
the server selector unit and connect them directly to the failing server. Then, 
run the server diagnostic programs on the failing server.
If the problem still remains, disconnect the keyboard and mouse from the 
failing server and reconnect them to the server selector unit. Then, replace the 
server rack components in the following order until the problem goes away.
a.
Device cable (connects between the server selector unit and the server 
that was selected when the failure occurred).