DC-to-DC Converter
The DC-to-DC converter utilizes energy from the battery system and raises 
the DC voltage to the optimum operating voltage for the inverter. This allows 
the inverter to operate continuously at its optimum efficiency and voltage, 
thus increasing reliability.
Battery
The Liebert GXT2U utilizes valve-regulated, nonspillable lead acid batteries. 
To maintain battery design life, operate the UPS in an ambient temperature 
of 68°F to 77°F (20°C to 25°C). Optional external battery cabinets are 
available to extend battery run times.
Dynamic Bypass
The Liebert GXT2U provides an alternate path for utility power to the 
connected load in the unlikely event of a UPS malfunction. Should the UPS 
have an overload, overtemperature, or UPS failure condition, the UPS 
automatically transfers the connected load to bypass. Bypass operation is 
indicated by an audible alarm and illuminated amber Bypass LED (other 
LEDs may be illuminated to indicate the diagnosed problem). To manually 
transfer the connected load from the inverter to bypass, press the Standby 
button once.
NOTE
The bypass power path does NOT protect the connected equipment 
from disturbances on the utility supply.