Emerson GXT2U User Manual

Page of 40
14
C
ONTROLS
 
AND
 I
NDICATORS
ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three 
functions:
• ON
• Alarm Silence
• Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide 
conditioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one second. 
After the alarm is silenced, the Liebert GXT2U will reactivate the alarm 
system to alert of additional problems.
Manual Battery Test - To initiate a manual battery test, press the ON 
button for at least one second while operating from utility power with no 
alarm conditions present. 
• If only three of the five Battery LEDs illuminate, allow the UPS to recharge 
the batteries for 24 hours.
• After  24  hours,  retest the batteries.
• After the batteries have been retested, if only three of the five Battery 
LEDs illuminate, contact your local dealer, Liebert representative or Lie-
bert Worldwide Support Group.
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be 
silenced.
All LEDs illuminated
for illustrative purposes only.