Troubleshooting
Liebert
®
 GXT3
32
11.0 T
ROUBLESHOOTING
This section indicates various UPS symptoms a user may encounter and provides a troubleshooting 
guide in the event the UPS develops a problem. Use the following information to determine whether 
external factors caused the problem and how to remedy the situation.
11.1 UPS Symptoms
The following symptoms indicate the Liebert GXT3 is malfunctioning:
• The relative indicators illuminate, indicating the UPS has detected a problem.
• An alarm buzzer sounds, alerting the user that the UPS requires attention.
11.1.1 Indicators
In addition to the fault indicator being illuminated, one or more of LED segments of battery level 
indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 20. The 
descriptions are listed in Table 4.
Figure 20 Battery level indicator
Table 4
Indicator descriptions
 Indicator
Diagnosis/Audible alarm
A - E
On bypass from output overload (half-second beep every half second)
A
On bypass due to overtemperature condition (1-second beep every 4 seconds)
B
On bypass due to DC bus overvoltage (1-second beep every 4 seconds)
C
On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)
D
PFC failure (1-second beep every 4 seconds).
E
On bypass due to inverter failure (1-second beep every 4 seconds)
A&C
UPS failed battery test (2-second beep every 60 seconds)
C&E
UPS shutdown by command from communication (USB port or Liebert IntelliSlot
®
 port) (no 
audible)
A&B
UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery 
charger failure) and continuous alarm
Battery Indicator
Flashing
Internal Battery source not available (continuous horn); check battery connection, power down 
and reboot UPS.
Bypass Indicator
Flashing
Mains power voltage or frequency is out of tolerance; bypass is unavailable
A - E indicators are shown in Figure 20
A
B
C
D
E