Emerson 1000 User Manual

Page of 32
Communication
20
6.4
UPS Communications
The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication 
and monitoring options.
Liebert MultiLink software continually monitors the UPS and can shut down your computer or server 
via USB, contact closure and SNMP (via IS-WEBRT3 card) in the event of an extended power failure.
The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across 
the network.
6.5
UPS Inverter/Transfer Voltage Configurations
A two-pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt-
ages of 110V, 120V or 127V. This feature will change the high and low points at which the UPS 
switches to battery power. It also changes the UPS’ output voltage when the UPS is operating in bat-
tery mode. The factory default setting is 120 VAC.
Turn Off the UPS before making any changes to the voltage configuration.
Figure 17 DIP switch settings for 120V system
NOTE
The USB, SNMP and contact closure communications can operate in parallel.
Table 5
Voltage configurations
Setting
Input Voltage Range
Output Voltage (Battery Mode)
110
83~138
110VAC
120
90~150
120VAC
127
96~159
127VAC
12
ON
FUNCTION
2
1
Voltage = 110V
Voltage = 120V
Voltage = 120V
Voltage = 127V