Troubleshooting
26
9.0
T
ROUBLESHOOTING
The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe-
riences a problem. See Table 9 for suggested solutions.
1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for 
low battery, overload warning and fault.
2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator, 
as described below:
If the UPS fails to operate properly, turn Off the unit and repeat the steps in 3.0 - Installation. If the 
problem persists, refer to Table 9.
Table 9
Troubleshooting—problems, causes and solutions
Problem
Cause
Solution
UPS will not start
Short circuit
Check the circuit breaker on the 
rear of the UPS.
If it is tripped, reset it and restart the 
UPS. For help, contact your local 
dealer, local Emerson 
representative or Channel Support 
Applications.
Battery is disconnected or 
completely discharged
Check for proper connection of 
battery or batteries.
UPS starts on battery, but will not 
switch to AC (dark start)
UPS not plugged in
Plug in the power cord securely.
Circuit breaker tripped
Reset the circuit breaker and restart 
the UPS.
AC overvoltage
Wait until voltage drops to an 
appropriate level or have the utility 
power checked by a properly 
trained and qualified electrician.
UPS shuts down
Short circuit or UPS output is 
abnormal; LED 10 and LED 11 
illuminate and sound audible 
alarm
Remove the load and turn on the 
UPS again. For help, contact your 
local dealer, local Emerson 
representative or Channel Support 
Applications.
Overload; LED 5 and LED 11 
illuminate and sound audible 
alarm
Check load level display and 
remove nonessential loads. 
Recalculate the load and reduce 
equipment connected to UPS - the 
total wattage must not exceed the 
capacity of the UPS.
LED 3 and LED 11 illuminate and 
sound audible alarm
Recharge the battery for 8 hours, 
then turn ON the UPS.
Liebert MultiLink software
Consult the Liebert MultiLink user 
manual or contact your LAN 
administrator.
Site Wiring Fault LED (LED 4) flashing
Site Wiring Fault, UPS detected a 
line-to-neutral reversal or a loss of 
proper grounding.
Have the utility checked by a 
properly trained and qualified 
electrician.
Battery weak LED (LED 3) flashing
Batteries weak
Recharge batteries.
Batteries need to be replaced
Replace batteries.
NOTE
The PS2200RT3-120XR UPS will sound an Overload alarm under certain Low Line 
conditions when it is fully loaded and it exceeds the input current rating. Unless the load is 
reduced, the condition will trip the branch circuit breaker.