10/38 Installation 
Guide 
SG Series 225 & 300 kVA 
3 INSTALLATION 
3.1 TRANSPORT 
Transport UPS only in upright position! 
The UPS is packaged on a pallet suitable for 
handling with a forklift. 
 
Pay attention to the center of gravity. 
 
The UPS must be moved in upright position
Do not tilt cabinets more than +/- 10° during 
handling. 
 
Move the UPS in it’s original package to the 
final destination site. 
 
Do not stack other packages on top
This could damage the UPS. 
 
If the UPS must be lifted by crane, use suitable 
lifting straps and spreader bars. 
Note of the center of gravity marked on the 
package.
 
Forklift 
 
 
Crane 
 
Fig. 3.1-1   UPS cabinets moving
 
Check for sufficient floor and 
elevator loading capacity.
 
 
3.1.1 Dimensions 
and 
weight 
 
Dimensions 
SG Series 225 and 300 kVA 
(W x D x H) 
64.96 x 31.50 x 70.90 inches 
1,650 x 800 x 1,800 mm 
S
G
S
_225
-30
0_U
P
S
 d
im
ens
ions
_GE
_0
1US
H
W
D
 
Fig. 3.1.1-1   UPS cabinet dimensions
 
 
 
Weight 
SG Series 225 and 300 kVA 
UPS rating 
Weight 
lbs / kg 
Floor loading 
lbs/sq.ft - kg/m
2
 
SG Series 225 kVA 
2,756 / 1,250 
194 / 947 
SG Series 300 kVA 
3,087 / 1,400 
218 / 1,061 
P.S.: Weights including the 5th harmonic filter.