GT Model 
 
1000T UL 
1500T UL  2000T UL 
3000T UL 
Capacity 
 
1kVA/800W  
1.5kVA/ 1200 W 
2kVA/1600W 
 
3kVA/2400W  
Rated Voltage 
100V, 110V, 120V 
Voltage Range 
80V~138V (full load); 65V ~80V  (70% load) 
Frequency 
50Hz / 60Hz (± 4.8 Hz) 
Input 
Power Factor 
0.97 
Voltage 
100V, 110V, 120V 
Frequency 
50Hz / 60Hz 
Voltage Regulation 
± 2% 
Frequency Accuracy 
± 0.05 Hz 
Wave Form 
pure sine wave 
Transient Response 
± 8% (10%
90% linear load) 
THD (linear load) 
3% 
3% 
4% 
THD (computer load)  
6% 
Overload Capacity  
105%~125% for 3mins; 125%~150% for 30secs; >150% for 1sec 
Crest  Factor  
3:1 
Output 
Efficiency (AC-A C) 
 87% 
Outlet 
Receptacles  
NEMA TYPE 
Battery Voltage 
36V  
72V  
72V 
Battery Type (Lead acid) 
12V/7Ah 
12V/7Ah 
12V/9A h 
Back-up Time 
(Typical) 
5mins 
 
Battery 
Recharge Time 
4~6 hours after complete discharge to recover 90%  
Transfer 
Time 
Transfer Time 
zero 
LED Status 
On- line / Bypass / On- battery / Overload / Battery Low / Fault 
Battery Replace / Battery Level / Load Level 
LED 
Alarm 
buzzer  
DB9 
RS232/dry contact 
Interface 
SNMP Slot 
internal 
Noise (At 1 Meter) 
40dB(A) 
42dB(A) 
45dB(A) 
Operating 
Temper ature 
0~40°C (32~104°F)  
Environment 
Humidity 
0%~90% (non-condensing) 
Safety  
UL/cUL 
EMC 
FCC Class A (2, 3kVA) /B (1kVA) 
CISPR PUB 22 Class B; TUV/EMC; CE (1kVA) 
CISPR PUB 22 Class A (2, 3kVA) 
Safety 
Approval 
Lightning 
IEEE 62.41 Category A 
Battery Start 
yes 
Extended Battery 
Bank 
yes (optional for longer runtime)  
Others 
Long Time Model 
yes (optional) 
Dimensions 
(W
×D×H) 
140x366x242 mm 
5.5x14.4x9.5 inch 
140x425x373mm 
5.5x16.7x14.7 inch 
Appearance 
Weight 
15 kg 
33 lbs 
30 kg 
66 lbs 
30 kg 
66 lbs  
 
 