Fluke 1743 User Manual

Page of 73
1744/1743 
Users Manual 
26 
  Time-activated job: The Logger starts logging as soon as the 
preprogrammed start time is reached, and stops at the defined end 
time. 
  Immediate job: The Logger starts logging as soon as power is on. 
Note the following about logging jobs: 
  The connection can be verified using the logging channel LEDs. If all 
three LEDs are lit continuously, the connection and the signal levels 
are within nominal range. For details, see Table 4 in the Features 
section. 
  The unit/job status is indicated by the status LED. For details, see 
Table 4 in the Features section. 
Completing the Logging Job 
1.  Terminate the job as follows: 
  For switch-activated jobs: At the end of the logging period, stop 
the logging job by pressing the START/STOP button. 
  For time-activated and immediate jobs: Stop the job in PQ Log 
with the         icon, or with menu Logger/Stop logging.  
Note 
Make sure the logging job is stopped with the START/STOP button 
(switch-activated jobs) or PQ Log (time-activated jobs) before the test 
leads or power supply leads are removed. Otherwise, the Logger will 
record a voltage interruption. 
Only switch-activated jobs can be aborted. Time-activated jobs are 
terminated only when the programmed measuring time has elapsed. 
2.  Remove the test leads of the three phases. Be sure to remove the 
measuring cable of the neutral wire last
3.  Remove the current probes.