Cisco Systems 124792 User Manual

Page of 96
1-7
Cisco AC/DC Power System User Guide, R1.0
May 2006
Chapter 1      Introduction
1.1.6   General Specifications
 provides status and alarm specifications for the Cisco AC/DC Power System.
 provides mechanical specifications of the Cisco AC/DC Power System.
 provides environmental specifications for the Cisco AC/DC Power System.
 provides compliance specifications for the Cisco AC/DC Power System.
Table 1-4
Protection Specifications
Protection
Description
Overcurrent (output)
Short circuit and automatic current limiting
Overvoltage 
Selective shutdown of modules at excessive 
output voltages
Table 1-5
Status and Alarm Specifications
Status & Alarms
Description
Alarm Contacts
Four form-C alarm contacts (Low Voltage, Mains 
Error, Module Failure, Fuse/Circuit Breaker 
Failure), maximum 60 VDC, rated at 1A
Status (Rectifier)
Green LED indicates power is within acceptable 
range
Yellow LED indicates current limit/thermal 
protection
Red LED indicates overvoltage shutdown or 
rectifier alarm
Table 1-6
Mechanical Specifications
Mechanical
Description
Shelf Dimensions 
WxHxD
17.4 x 5.25 x 10.8in. (442 x 132.9 x274mm)
1RU Shelf WxHxD
17.1 x 1.69 x 9.175in. (434 x 43 x 233mm)
Mounting
ETSI, 19in. (IEC and ANSI) or 23in.
Table 1-7
Environmental Specifications
Environment
Description
Shock/Vibration
(NEBS) Level 3, Class B Certification
Earthquake
Zone 4 Compliant
Audible Noise
<60 dBA
Ambient Temperature
-40°C to 55°C 
Storage Temperature
-40°C to +85°C 
Relative Humidity
10-90%, non-condensing