Page of 16
Dell UPS Local Node Manager 
USER'S GUIDE EXTENSION FOR MICROSOFT VIRTUAL ARCHITECTURES 
Dellups.com 
 
Dell ULNM - User guide extension - HyperV R1 & R2 
rev0.01 
CHAPT
ER:
 
In
sta
llat
ion
 
14
 
 
 
 
 
 
 
2.9.2.  STEP 2 (CONFIGURATION) 
 
When started, the application automatically performs a Quick scan. 
 
Using the Quick scan operation, you will discover: 
 
=>Serial line connected UPSs (RS232 or USB)  
The discovered UPS connected  through (RS232 or USB) is automatically assigned as the 
Power source (the Status icon is Green 
 
=> Networked UPSs through broadcast within a few seconds (Dell UPS Management Card 
H910P)
 
The discovered UPS connected  through (Network) are not automatically assigned as the 
Power source (You have to select the node and click on the button Set as Power Source the 
icon becomes Green 
 
The discovered nodes are displayed in Settings 
 Auto Discovery 
 
 
For the other nodes, please perform the discovery based on IP address ranges (Range scan
 
Using the Range Scan operation you will discover the nodes that are outside of the Network 
segment and nodes that are not compatible with the ”Quick scan” feature. 
 
In the Settings 
 Shutdown page, assign the IP address of the UPS that powers the local Computer. 
 
In the Settings 
 User List page, assign the access rights through “login and password”