DELL 5600W User Manual

Page of 8
Dell UPS Site Preparation Guide, EMEA (230V) 
 
Revision 2, December 2012 
4200W Rack 
Online 
210 / 717 
420 / 1434 
5600W Rack 
Line Interactive 
280 / 956 
560 / 1921 
5600W Rack 
Online 
390 / 989 
420 / 1433 
10kW Rack 
Online 
412 / 1420 
754 / 2600 
 
Optional accessories for Dell UPS 
Optional Accessory 
Importance 
Purpose & Use 
External Battery Module (EBM) 
Optional 
Increases the battery runtime (autonomy) by approximately 3 times 
Network Management Card 
(NMC) 
Recommended 
Improves communication with >1 server and is mandatory for 
virtualization
 
Environmental Monitoring Probe 
(EMP) 
Recommended 
Measures rack temperature and humidity (plus 2 x relay contacts).  
Requires network management card.  Data rolls up into UPS Management 
software. 
32 Amp, 3m (non-locking) 
Electrical Input Cord
1
 
Highly Recommended 
UPS input cable pack providing a 3m cord with IEC309 32A (IEC60309 
332P6S, non-locking, IP44 type) Commando plug.  Also includes plastic 
stuffing gland (strain relief). 
 
Rack Preparation: 
Rack Requirements for the Dell UPS
 
Dell Rack UPS are suitable for installation into 19” 4-post racks. Reserve space for UPS and EBM at bottom of rack.  
Rack types supported are: EIA/ECA-310-E (includes Dell and other common rack suppliers); and, support 4-post 
square or round (non-threaded) type holes. If round hole, use rack with 7.0mm diameter (unthreaded). The Dell rack 
UPS and rack EBM include ReadyRails with a minimum retraction of 517 mm (20.35") and maximum extension of 783 
mm (30.8"). 
Electrical Preparation: 
Electrical Requirements for the Dell UPS 
UPS Model 
UPS Technology 
Input Voltage (VAC) 
Power Draw 
(standby) 
 
Overcurrent 
Protection 
Minimum Wire Size 
(Live Neutral/Ground) 
3750W Rack 
Online 
208, 220, 230, 240 
186W 
 
25 Amp 1-phase 
5.26 / 5.26 mm
2
 
4200W Rack 
Online 
208, 220, 230, 240 
210W 
 
30 Amp 1-phase 
5.26 / 5.26 mm
2
 
5600W Rack 
Line Interactive 
208, 220, 230, 240 
224W 
 
32 Amp 1-phase 
8.36 / 5.26 mm
2
 
5600W Rack 
Online 
208, 220, 230, 240 
143W 
 
32 Amp 1-phase 
8.36 / 5.26 mm
2
 
10kW Rack 
Online 
208, 220, 230, 240 
60W 
 
63 Amp 1-phase 
21.14 / 8.36 mm
2
 
 
Note:
  Overcurrent protection should be ‘slow-break’, suitable for devices with a high inrush current.  Normally this should be a fuse or 
circuit breaker with a Type-C or Type-3 rating.
 
Electrical Requirements for the REPO Switch (Remote Emergency Power Off) 
REPO is used to shut down the UPS from a distance. For example, this feature can be used for shutting down the 
load and the UPS by thermal relay, in the event of room over-temperature. When REPO is activated, the UPS shuts 
down the output and all its power converters immediately. The UPS logic power remains on to issue an alarm. 
                                                           
1
Supported UPS are 3750W, 4200W (Online) and 5600W (Line Interactive) models.  5600W Online and 10kW Online UPSs do not 
have an input cord option