DELL 5600W User Manual
Dell UPS Site Preparation Guide, EMEA (230V)
Revision 2, December 2012
4200W Rack
Online
210 / 717
420 / 1434
5600W Rack
Line Interactive
280 / 956
560 / 1921
5600W Rack
Online
390 / 989
420 / 1433
10kW Rack
Online
412 / 1420
754 / 2600
Optional accessories for Dell UPS
Optional Accessory
Importance
Purpose & Use
External Battery Module (EBM)
Optional
Increases the battery runtime (autonomy) by approximately 3 times
Network Management Card
(NMC)
(NMC)
Recommended
Improves communication with >1 server and is mandatory for
virtualization
virtualization
Environmental Monitoring Probe
(EMP)
(EMP)
Recommended
Measures rack temperature and humidity (plus 2 x relay contacts).
Requires network management card. Data rolls up into UPS Management
software.
Requires network management card. Data rolls up into UPS Management
software.
32 Amp, 3m (non-locking)
Electrical Input Cord
Electrical Input Cord
1
Highly Recommended
UPS input cable pack providing a 3m cord with IEC309 32A (IEC60309
332P6S, non-locking, IP44 type) Commando plug. Also includes plastic
stuffing gland (strain relief).
332P6S, non-locking, IP44 type) Commando plug. Also includes plastic
stuffing gland (strain relief).
Rack Preparation:
Rack Requirements for the Dell UPS
Dell Rack UPS are suitable for installation into 19” 4-post racks. Reserve space for UPS and EBM at bottom of rack.
Rack types supported are: EIA/ECA-310-E (includes Dell and other common rack suppliers); and, support 4-post
square or round (non-threaded) type holes. If round hole, use rack with 7.0mm diameter (unthreaded). The Dell rack
UPS and rack EBM include ReadyRails with a minimum retraction of 517 mm (20.35") and maximum extension of 783
mm (30.8").
square or round (non-threaded) type holes. If round hole, use rack with 7.0mm diameter (unthreaded). The Dell rack
UPS and rack EBM include ReadyRails with a minimum retraction of 517 mm (20.35") and maximum extension of 783
mm (30.8").
Electrical Preparation:
Electrical Requirements for the Dell UPS
UPS Model
UPS Technology
Input Voltage (VAC)
Power Draw
(standby)
Overcurrent
Protection
Minimum Wire Size
(Live Neutral/Ground)
3750W Rack
Online
208, 220, 230, 240
186W
25 Amp 1-phase
5.26 / 5.26 mm
2
4200W Rack
Online
208, 220, 230, 240
210W
30 Amp 1-phase
5.26 / 5.26 mm
2
5600W Rack
Line Interactive
208, 220, 230, 240
224W
32 Amp 1-phase
8.36 / 5.26 mm
2
5600W Rack
Online
208, 220, 230, 240
143W
32 Amp 1-phase
8.36 / 5.26 mm
2
10kW Rack
Online
208, 220, 230, 240
60W
63 Amp 1-phase
21.14 / 8.36 mm
2
Note: Overcurrent protection should be ‘slow-break’, suitable for devices with a high inrush current. Normally this should be a fuse or
circuit breaker with a Type-C or Type-3 rating.
Electrical Requirements for the REPO Switch (Remote Emergency Power Off)
REPO is used to shut down the UPS from a distance. For example, this feature can be used for shutting down the
load and the UPS by thermal relay, in the event of room over-temperature. When REPO is activated, the UPS shuts
down the output and all its power converters immediately. The UPS logic power remains on to issue an alarm.
load and the UPS by thermal relay, in the event of room over-temperature. When REPO is activated, the UPS shuts
down the output and all its power converters immediately. The UPS logic power remains on to issue an alarm.
1
Supported UPS are 3750W, 4200W (Online) and 5600W (Line Interactive) models. 5600W Online and 10kW Online UPSs do not
have an input cord option
.