Delta Electronics VFD-EL User Manual

Page of 209
 
Revision August 2008, 2ELE, V1.02
 
6-1
 
Chapter 6 Fault Code Information and Maintenance
 
6.1 Fault Code Information 
The AC motor drive has a comprehensive fault diagnostic system that includes several different 
alarms and fault messages. Once a fault is detected, the corresponding protective functions will be 
activated. The following faults are displayed as shown on the AC motor drive digital keypad display. 
The five most recent faults can be read from the digital keypad or communication. 
NOTE
 
Wait 5 seconds after a fault has been cleared before performing reset via keypad of input terminal. 
6.1.1 Common Problems and Solutions 
Fault 
Name 
Fault Descriptions 
Corrective Actions 
 
 
Over current 
Abnormal increase in current. 
1. 
Check if motor power corresponds with the 
AC motor drive output power. 
2. 
Check the wiring connections to U/T1, V/T2, 
W/T3 for possible short circuits. 
3. 
Check the wiring connections between the AC 
motor drive and motor for possible short 
circuits, also to ground. 
4. 
Check for loose contacts between AC motor 
drive and motor. 
5. Increase 
the 
Acceleration Time. 
6. 
Check for possible excessive loading 
conditions at the motor. 
7. 
If there are still any abnormal conditions when 
operating the AC motor drive after a short-
circuit is removed and the other points above 
are checked, it should be sent back to 
manufacturer. 
 
Over voltage 
The DC bus voltage has 
exceeded its maximum 
allowable value. 
1. 
Check if the input voltage falls within the 
rated AC motor drive input voltage range. 
2. 
Check for possible voltage transients. 
3. 
DC-bus over-voltage may also be caused by 
motor regeneration. Either increase the 
Decel. Time or add an optional brake resistor 
(and brake unit). 
4. 
Check whether the required brake power is 
within the specified limits.