Delta Electronics VFD-EL User Manual

Page of 209
Appendix B  Accessories|  
B-12 
Revision August 2008, 2ELE, V1.02 
B.5 Zero Phase Reactor (RF220X00A)  
Dimensions are in millimeter and (inch) 
  
  
   
       
Recommended Wire 
Size 
Cable 
type 
(Note)   AWG mm
2
 
Nominal 
(mm
2
Qty.
Wiring 
Method
10  ≦5.3 
5.5 
Diagram 
Single-
core 
2  ≦33.6  ≦38 
Diagram 
12  ≦3.3 
3.5 
Diagram 
Three-
core 
1  ≦42.4  ≦50 
Diagram 
Note: 600V Insulated unshielded Cable. 
 
 
 
Power
Supply
Zero Phase Reactor
MOTOR
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
 
 
 
 
 
 
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Power
Supply
Zero Phase Reactor
MOTOR
 
Note 1: The table above gives 
approximate wire size for the zero phase 
reactors but the selection is ultimately 
governed by the type and diameter of 
cable fitted i.e. the cable must fit through 
the center hole of zero phase reactors. 
 
 
Note 2: Only the phase conductors should 
pass through, not the earth core or screen. 
 
 
Note 3: When long motor output cables 
are used an output zero phase reactor 
may be required to reduce radiated 
emissions from the cable. 
 
Diagram B 
Please put all wires through 4 cores in 
series without winding. 
Diagram A 
Please wind each wire 4 times around the 
core. The reactor must be put at inverter 
output as close as possible.