Revision August 2008, 2ELE, V1.02
 
 
2-1
 
Chapter 2 Installation and Wiring 
After removing the front cover, check if the power and control terminals are clear. Be sure to observe 
the following precautions when wiring. 
 
„ General 
Wiring 
Information 
Applicable Codes 
All VFD-EL series are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters 
Laboratories (cUL) listed, and therefore comply with the requirements of the National 
Electrical Code (NEC) and the Canadian Electrical Code (CEC). 
 
Installation intended to meet the UL and cUL requirements must follow the instructions 
provided in “Wiring Notes” as a minimum standard. Follow all local codes that exceed UL 
and cUL requirements. Refer to the technical data label affixed to the AC motor drive and 
the motor nameplate for electrical data. 
 
The "Line Fuse Specification" in Appendix B, lists the recommended fuse part number for 
each VFD-EL Series part number.  These fuses (or equivalent) must be used on all 
installations where compliance with U.L. standards is a required. 
 
CAUTION!
 
1. 
Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals. Failure to comply may 
result in damage to the equipment. The voltage and current should lie within the range as 
indicated on the nameplate. 
2. 
All the units must be grounded directly to a common ground terminal to prevent lightning strike 
or electric shock. 
3. 
Please make sure to fasten the screw of the main circuit terminals to prevent sparks which is 
made by the loose screws due to vibration. 
4. 
Check following items after finishing the wiring: 
A.  Are all connections correct? 
B.  No loose wires?
 
C.  No short-circuits between terminals or to ground?