Chapter 4 Parameters| 
4-26
 
Revision August 2008, 2ELE, V1.02
 
4.3 Description of Parameter Settings 
Group 0: User Parameters                                    This parameter can be set during operation.
00.00 
Identity Code of the AC Motor Drive  
 
Settings 
Read Only 
Factory setting:  ##
00.01 
Rated Current Display of the AC Motor Drive 
 
Settings 
Read Only 
Factory setting:  #.#
 
Pr. 00.00 displays the identity code of the AC motor drive. The capacity, rated current, rated 
voltage and the max. carrier frequency relate to the identity code. Users can use the following 
table to check how the rated current, rated voltage and max. carrier frequency of the AC motor 
drive correspond to the identity code. 
 
Pr.00.01 displays the rated current of the AC motor drive. By reading this parameter the user 
can check if the AC motor drive is correct. 
115V/230V Series 
kW 0.2 
0.4 
0.75 1.5  2.2  3.7 
HP 0.25 
0.5 
1.0 2.0 3.0 5.0 
Pr.00-00 
0 2 4 6 8 10 
Rated Output 
Current (A) 
1.6 2.5 4.2 7.5 11.0 17.0 
Max. Carrier 
Frequency 
12kHz 
 
460V Series 
kW 0.4 
0.75 
1.5 2.2 3.7 
HP 
0.5 1.0 2.0 3.0 5.0 
Pr.00-00  3 5 7 9 11 
Rated Output 
Current (A) 
1.5 2.5 4.2 5.5 8.2 
Max. Carrier 
Frequency 
12kHz 
 
00.02 
Parameter Reset  
 
 
 
 
Factory Setting:  0
 
Settings  0 
Parameter can be read/written 
 
 
All parameters are read-only 
   8 
Keypad 
lock 
 
 
All parameters are reset to factory settings (50Hz, 230V/400V or 
220V/380V depends on Pr.00.12) 
 
 
10  All parameters are reset to factory settings (60Hz, 115V/220V/440V)