DELL H950N User Manual

Page of 71
51
 
Operation
|
Configuring Automatic on Battery Shutdown
If set to Off (default), the load segment turns off only when commanded manually by the 
 button,
an external command, or through the display (Control > Load Segments).
If set to zero seconds (0s), the load segment turns off automatically when the UPS on Battery state
activates.
If you select a value, the load segment turns off automatically after the selected delay while the UPS
operates on battery, but the shutdown is cancelled if the utility returns before the delay has expired.
To set the shutdown times for each load segment:
1
Press the 
 
button for one second to go to the main menu selection and scroll down to the
Settings menu using the   button.
2
Press the 
 button to enter the Settings menu.
3
Use the   button to scroll to the Automatic on Battery Shutdown option and press the 
 button.
The options display and the current settings flash when selected.
4
Set the shutdown delay for one load segment using the   and   buttons.
5
Press the 
 button to confirm.
6
Set the shutdown delay for the other load segment if applicable.
7
Press the 