Installation
|
5
Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.
Strip 0.5” (1.5 cm) of insulation from the end of each incoming wire.
6
Figure 21. UPS Input Terminal Block
Table 1. UPS Wiring Specifications
Wire
Function
Terminal
Position
UPS Wire Function
Terminal Wire
Size Rating*
Tightening
Torque
Input
1
Input Ground
5.26–16 mm
2
(10–6 AWG)
2.26 Nm (20 lb in)
2
L2/Neutral In
3
L1 In
* Use 5.26 mm
2
 (10 AWG) 75
_C copper wire minimum.
7
Replace the terminal block cover.
8
Continue to the following section, “UPS Initial Startup.”
UPS Initial Startup
To start up the UPS:
1
Verify that the internal batteries are connected.
2
If an optional EBM is installed, verify that the EBM is connected to the UPS.
3
Verify that all load segment circuit breakers are in the ON position.