Behavior on Overload
Table 7. Behavior on Overload
Overload
Severity
Load Level
On Utility Power
On Bypass/High
Efficiency Mode
On Battery
Level 1
Load 100% to
101%
Overload alarm only and
support load indefinitely
Overload alarm only
and support load
indefinitely
Overload alarm only,
support load until low
battery shutdown level
is reached
Level 2
Load 102% to
110%
Transfer to Bypass after
12 seconds (±1 sec)
If Bypass is not available,
transfer to Fault mode after
12 seconds (±1 sec)
Transfer to Fault mode
in 2 minutes (±1 sec)
Transfer to Fault mode
after 12 seconds
(±1 sec) or until low
battery shutdown level
is reached
Level 3
Load > 110% Transfer to Bypass immediately
If Bypass is not available,
transfer to Fault mode in
300 ms to 1 sec
Transfer to Fault mode
in 300 ms to 1 sec
Transfer to Fault mode
in 300 ms to 1 sec