DELL 2300W User Manual

Page of 73
50
|
Operation
Retrieving the Event Log
To retrieve the Event Log through the display:
1
Press the 
 
button for one second to go to the main menu selection and scroll down to the
Event Log menu using the   button.
2
Press the 
 button to enter the Event Log list.
3
Scroll through the listed events, notices, and alarms using either the 
 
button or the   button.
4
To return to the main menu, press the 
 
button for one second. The Event Log displays.
5
Press the   button. The UPS status screen displays.
Behavior on Overload
Table 8. Behavior on Overload
Overload Severity
Load Level
On Utility Power
On Battery
Level 1
100% to 101%
Overload alarm only and
support load indefinitely
Overload alarm only, support load until
low battery shutdown level is reached
Level 2
102% to 110%
Transfer to Fault mode in
2 minutes (±1 sec)
Transfer to Fault mode in 12 seconds
(±1 sec) or until low battery shutdown
level is reached
Level 3
> 110%
Transfer to Fault mode in
300 ms to 1 sec
Transfer to Fault mode in 300 ms to
1 sec