ADC 70 User Manual

Page of 32
ADCP-80-524 • Issue 1 • November 2001
Page 27
©
 2001, ADC Telecommunications, Inc.
Figure 21. Wire Wrap Alarm Contact Connection 
4.10 Input Power Connectors
Connect
 the input power wires to the input power connectors labeled “BATT” and connect the
return
 wires to the return connectors labeled “RTN” for both buses in the fuse panel as shown in
.
 Connect input power to the appropriate power sources in accordance with applicable
local
 electrical codes and/or National Electrical Codes but do not apply power to the panel
until
 directed to do so. 
 
• Compression
  lug  connectors:  Use  the  included  2-hole  lugs  with  #6  AWG  copper  wire
(insulation
 stripped back) or optional 2-hole lugs available as accessories with appropriate
AWG
 copper wire. Tighten the nuts to approximately 16 pound-force inches (1.8 Newton
meters).
Note:
 Before connecting the input or output power wires, measure the resistance at each
bus
 input connector as specified in 
Caution:
 Connect only the input voltage wire [the wire labeled BATTERY or BATT, or labeled
with
 the negative () voltage polarity and/or the voltage value] to the connector on the fuse
panel
  labeled  BATT  (battery).  Connect  only  the  input  return  wire  [the  wire  labeled  RTN,
RETURN,
 or BATTERY GROUND, or labeled with the positive (+) voltage polarity] to the
connector
 on the fuse panel labeled RTN (return). 
Caution:
 Caution should be taken to not reverse input wires to the fuse panel. Within the fuse
panel,
 the internal battery (negative voltage) wiring is protected and the internal return wiring
is
 not protected by fuses. If the wires are reversed, voltage could be present on the fuse panel
chassis
 and current could flow through the unprotected return wiring in the fuse panel. This
condition
 can cause damage to equipment in the frame in which the fuse panel is installed and
to
 equipment in adjacent frames
16161-B
 
CONNECT TO
APPROPRIATE
TERMINALS
OF ALARMS
 
CONNECT TO
APPROPRIATE
TERMINALS
OF ALARMS
WRAP TERMINAL BLOCK PINS USING  #22 TO #26 AWG COPPER WIRE  WITH INSULATION STRIPPED BACK.