3com 3C16021 User Manual

Page of 42
DUA1602-0AAA01
3-2
C
HAPTER
 3: C
ONFIGURING
 T
HE
 M
ANAGEMENT
 M
ODULE
Plug the other end of the serial cable into the serial port on the 
back of the terminal.
Press [Return]. The Main Configuration screen for the module type 
appears (
 or 
If the Main Configuration screen does not appear, press [Return] 
and make sure the Management Module is properly connected to 
the UPS (see “Installing the Management Module”).
If you still do not see the Main Configuration screen, check the 
following conditions:
Check the communications settings of the terminal you are 
using. It should be set to 9600 baud, No parity, 8 bits, and 1 
stop bit.
If the serial configuration is correct, check the cable between 
the module and terminal to be sure all connections are secure.
Make sure your terminal program is on the correct 
communications port for your RS-232 connection.
Verify that the management power cable is connected to the 
UPS.
Using the Configuration Screens
Each version of the Management Module has its own configuration 
screen. When you start the configuration program, the Main 
Configuration screen for your module appears. Figure 3-1 shows 
the screen for the Ethernet module. Figure 3-2 shows the screen 
for the Token-Ring module.
The Main Configuration screen shows the current configuration 
settings for your Management Module. A list of command (CMD) 
options are available in the left column of the screen.