(3)  Power supply environment 
If the UPS is used in an environment subject to long and frequent power outages (more than 
once a week), the batteries may not receive sufficient charge, which could result in 
foreshortened battery life and premature battery failure. 
(4)  If the UPS is not operated for a long period, the batteries may require recharging. Operate 
the UPS with no load to recharge the batteries as indicated in the following table, according 
to the storage temperature. If the batteries in the UPS are left uncharged, their service life 
will be greatly foreshortened. 
 
Storage Temperature 
Charge Interval 
No-Load Operation 
25°C (77°F) 
Once every 6 months 
At least 20 hours 
30°C (86°F) 
Once every 4 months 
At least 20 hours 
40°C (104°F) 
Once every 2 months 
At least 20 hours 
 
(5) Insulation testing 
Before testing indoor wiring insulation, shut down the UPS and disconnect the input and 
output cables. Conducting an insulation test with the UPS connected may damage electronic 
components such as the built-in arrester. 
(6) Rack support rails (not supplied) are required to mount the UPS on a rack. For details, 
contact your supplier or Sanyo Denki representative. 
 
2.4 Dealing with Errors 
Contact your supplier or Sanyo Denki representative if any of the following occur. 
(1)  The red ALARM indicator lights (except when the UPS stops because of a prolonged power 
outage). 
(2)  The green INV.ON/STAND BY indicator, green INPUT indicator, or green OUTPUT indicator 
does not light even when the UPS is operated properly. 
(3)  Another condition occurs which you suspect is caused by a failure in the UPS. 
 
 
 
3. Checking the Contents of the Package 
 
After opening the package carton, check to be sure that it contains all of the following 
items. If any item is missing, contact your supplier or Sanyo Denki representative. 
 
(1) UPS 
(2) Accessories  Instruction Manual (this manual) 
  
Network 
cable 
 
 
Rack mounting bracket (Right) 
1   
 
 
Rack mounting bracket (Left) 
1   
 
 
Screws for Rack mounting brackets 
4   
  
Bushings 
  
Stands 
 
 
Screws for Stands 
4   
 
 
Power Management Software disc (CD-ROM) 
 
 
(
SANUPS SOFTWARE STANDALONE)
     
 
 
 
The installation guide and the user guide are installed in CD-ROM
 
 
 
 
* Note about sale or transfer of ownership 
If you sell the UPS or transfer ownership to a third party, all accessories and other 
items supplied with the UPS must be sold or transferred together with the UPS.