4.  Clear Text Display Module & System Parameters
English
© STÖBER plc 1997
27
05.02.01
Parameter Function
Range
[Default]
Description / Notes
P910  
••••
Local/Remote mode
0 - 4
[0]
Sets the inverter for local control or remote control over the serial link:
0 = Local control
1 = Remote control (and setting of parameter values)
2 = Local control (but remote control of frequency)
3 = Remote control (but local control of frequency)
4 = Local control (but remote read and write access to
parameters and facility to reset trips)
Note:
When operating the inverter via remote control (P910 = 1
or 3), the analogue input remains active when P006 = 1
and is added to the setpoint.
P918  
••••
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details
(Access only possible with P099 = 1.)
P922
Software version
0.00 -
99.99
[-]
Contains the software version number and cannot be changed.
P923  
••••
Equipment system number
0 - 255
[0]
You can use this parameter to allocate a unique reference number to
the inverter. It has no operational effect.
P927  
••••
P928  
••••
P930
Most recent fault code
0 - 9999
[-]
The last recorded fault code (see section 5) is stored in this
parameter. It is cleared when the inverter is reset.
P931
Most recent warning type
0 - 9999
[-]
The last recorded warning is stored in this parameter until power is
removed from the inverter:
002 = Current limit active
003 = Voltage limit active
005 = Inverter over temperature (internal PTC)
P944
Reset to factory default settings
0 - 1
[0]
Set to ‘1’ and then press P to reset all parameters except P101 to the
factory default settings.
P947
P958
P963
P967
P968
P970
P971  
••••
EEPROM storage control
0 - 1
[1]
0 = Changes to parameter settings (including P971) are lost when
 
power is removed.
1 = Changes to parameter settings are retained during periods
when power is removed.
IMPORTANT
Take care not to exceed the EEPROM write cycle limit of
50,000/parameter (approx.) when using the serial link to update
parameters, otherwise data loss or corruption may occur. Read cycles
are unlimited.
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Access only possible with P099 = 1.)
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details. (Cannot be accessed unless P099 = 1.)