Panasonic A4P Series User Manual

Page of 232
130
Sequential Operation
Sequential Operation
The sequential operation can be performed by setting 16.Pr52 (sequential operation setting) to “1”. When
the sequential operation is set, execute a step operation by incrementing a point number by 1 at every
inputting the strobe signal input (STB: CN X5 Pin 24) when the servo turns on, not using the point specifying
input (P1IN to P32IN: CN X5 Pin 3, 4, 5, 6, 7 and 8).
• Homing operation at sequential operation
1) 16.Pr38 (homing disabling setting) is “0” (homing required) and an operation mode is not the absolute
mode (SV.Pr0B (absolute encoder setting) is “1”).
=> Homing is executed by the first strobe signal input (STB) after the power supply turns on.
A sequential operation is performed beginning with the point 1 after the next strobe signal.
2) 16.Pr38 (homing disabling setting) is “1” (homing not required) and an operation mode is the absolute
mode (SV.Pr0B (absolute encoder setting) is “0” or “2”).
=> A sequential operation is performed beginning with the point 1 when the first strobe signal is input,
because homing is not required.
A maximum point number of the sequential operation can be set by 16.Pr53 (a maximum point number of
sequential operation). After a step operation of the maximum point number is executed, the operation re-
turns to the point 1. In the sequential operation, the maximum point number can be specified in a range
between 1 and 60, because the setting of SV.Pr57 (selection of number of input points) is disabled.
Example of Operation
16.Pr52 (sequential operation setting) = 1 (enabled)
16.Pr53 (a maximum point number of sequential operation) = 3
Power supply 
turns on
STB
Homing
operation
Open
Close
1st time 
= homing 
   operation
2nd time 
= Operation 
   at point 1
3rd time 
= Operation 
   at point 2
4th time 
= Operation at point 3
5th time 
= Operation at point 4
Point 1
Point 1
Point 3
Point 2
Setting of parameter
Power reset
Execution of homing 
operation
Designation of 
operation point 
number
Description
Set 16.Pr52 (sequential operation setting) to “1” and necessary positioning parameters to 16.Pr53 
(a maximum point number of sequential operation), “homing operation” and “step operation”.
Turn the servo on after the power supply turns on again.
Close the first open strobe signal input (STB). Then, homing is executed.
After that, an operation is performed in order at every inputting the strobe signal input (STB), e.g., 
point 1 –> point 2 –> point 3 –> point 1 –> point 2 –> ...
(1)
(2)
(3)
(4)
Procedure
Caution
1) When setting the sequential operation, an operation command (step operation, homing, jog operation or
Alarm Clear) cannot be executed by the point specifying input (P1IN to P32IN). However, the Alarm Clear
can be specified by assignment of the multifunction input 1/2 (EX-IN1/EX-IN2: CN X5 Pin 22/25).
2) A block operation is unavailable when the sequential operation is set.