Panasonic A4P Series User Manual

Page of 232
44
System Configuration and Wiring
List of Signal for Connector CN X5
Common input signals
Application
Code
Function
Connector
pin No.
Control signal 
power supply
COM+
COM–
1
17
• Connected to the  +  terminal of an external DC power supply (12 to 24 V)
• Use a 12 V (
±
5%) to 24 V (
±
5%) power supply.
• Connected to the  –  terminal of an external DC power supply (12 to 24 V).
• The power supply capacity differs depending on the configuration of the 
input/output circuits used. A capacity of more than 0.5A is recommended.
Emergency 
stop input
EMG-
STP
2
• When connection with COM– is opened, emergency stop input error (error 
code No.39) occurs, and the circuit trips.
• Tripping can be reset using an alarm clear input initiated by specifying point 
0 or assigning the multi-function inputs (EX-IN1, EX-IN2).
Point specifying 
input
• Specify an operation point number when operation command is input.
• The number at which operation point can be specified depends on the 
number of points set by SV.Pr57.
• SV.Pr58 can be used for setting input logic.
  When the point described below is specified, special operation is 
performed.
1)Specify point 0, and input a strobe signal, then alarm is cleared.
2)Specify the maximum point number specified in SV.Pr57, and input a 
strobe signal, then system returns to the home position.
3)Specify the maximum point number specified in SV.Pr57 –1 and input a 
strobe signal, then high-speed normal rotation jog is performed.
4)Specify the maximum point number specified in SV.Pr57 –2 and input a 
strobe signal, then high-speed reverse rotation jog is performed.
CCW over-
travel
inhibit input
CCWL
19
• CCW drive prohibition input (CCWL).
• Connect so as to open COM– connection when movable part of the 
equipment exceeds the movable range in CCW direction.
• When this input is open, operation command in CCW direction is not 
issued. (Torque is generated)
• SV.Pr53, 54, and 55 enable for setting of valid/invalid, input logic, and 
operation.
P1IN
P2IN
P4IN
P8IN
P16IN
P32IN
3
4
5
6
7
8
CW over-travel
inhibit input
CWL
20
• CW drive prohibition input (CWL).
• Connect so as to open COM– connection when movable part of the 
equipment exceeds the movable range in CW direction.
• When this input is open, operation command in CW direction is not issued. 
(Torque is generated)
• SV.Pr53, 54, and 55 enable setting of valid/invalid, input logic, and 
operation.
Home sensor 
input
Z-LS
21
• Connect so as to close the home sensor input when system is in the 
vicinity of home position (default).
  SV.Pr56 can be used for setting input logic.
• Connected to the home sensor signal.
Servo-ON sig-
nal input
SRV-ON
23
• Connect so as to close the home sensor input when system is in the 
vicinity of home position.
  Pr56 can be used for setting input logic.
• When servo driver is connected to COM– of control signal power supply, it is 
set in servo-ON condition.
• When connection to COM– is opened, servo-OFF condition is set, and 
energization of motor is cut off.
• Dynamic brake operation and deviation counter clearing operation in servo-OFF 
condition can be chosen by SV.Pr69 (sequence at servo-off).
• SV.Pr5D enable setting of valid/invalid.
<Notes>
1)When shifting from servo-OFF to servo-ON, make sure that the motor is 
stopped.
2)After shifting to servo-ON, allow 100ms or more before giving an 
instruction.
3)Frequent repeating of servo-ON/OFF may damage the dynamic brake 
circuit contained in servo driver. Avoid such a use.