Chapter 3  Monitor the Uninterruptable Power Supply    31
UPS Installation and Configuration Guide
Figure 7   UPS status report
7
To print the report, select Print this Report from the screen.
8
To close the report window, select Close This Window from the screen.
9
This procedure is complete.
Test the UPS
Use this procedure to test the UPS power backup function after you have installed and configured 
the UPS for the Business Communications Manager. 
The UPS device automatically performs a biweekly self-test. Locate the test results under the 
following path: 
 
F:\Program Files\PwerChute\PwrChute.log file.
1
Ensure that the serial cable between the Business Communications Manager and the UPS (or 
the expansion chassis) is securely connected at both ends.
2
Simulate a power failure. Disconnect the power cord from the AC power source (wall outlet) 
to the UPS device. 
3
Verify that the BCM connected to the UPS device remains operational