6.1 Technical specifications
  
  
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software.
(3) Adjustable to 200 V (10% derating of output power) / 208 V / 220 V / 230 V / 240 V.
(4) Battery Evolution S EXB 1250/1750: 2 strings, each 4 x 12 V / 9 Ah.
(5) Battery Evolution S EXB 2500/3000: 2 strings, each 6 x 12 V / 9 Ah.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16A, 250V which is  IEC/EN 
60898-1 standard compliant; 
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20A, 250V.
This product is designed for IT power distribution system.
 
Evolution S 
1250
Evolution S 
1750
Evolution 
2000
Evolution S 
2500
Evolution S 
3000
Output power
1250VA/1150W
1750VA/1600W
2000VA/1600W
2500VA/2250W
3000VA/2700W
AC input power
 Rated input voltage
 Input-voltage range
 Input-frequency range
Single phase 220~240 V
 160 V to 294 V 
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system) 
(2)
Output on battery power
 Voltage
 Frequency
230 V (+6/-10%) 
(3)
50/60 Hz ±0.1%
Battery (sealed lead acid, 
maintenance free)
  Standard
 Additional modules possible 
(up to 4 EXB)
4 x 12 V
7.2 Ah
4 x 12 V - 9 Ah
6 x 12 V
7.2 Ah
6 x 12 V
9 Ah
Evolution S EXB 1250/1750 
(4)
No
Evolution EXB S 2500/3000 
(5)
Environment
 Operating temperature 
range
 Storage temperature range
 Relative humidity
 Noise level
0 to 40°C
-25°C to 40°C
20 to 90% (without condensation)
< 45 dBA
< 50 dBA
Filter
Transformer
(AVR)
Charger
Inverter
Battery