MGE UPS Systems S 3000 RT 3U User Manual

Page of 22
34008236EN/AA
 - Page 16
4. Personalisation using external software  
Main-output personalisation 
Voltage-threshold personalisation 
(1) Low threshold for transfer to battery is 150 V.
UPS-sensitivity personalisation 
UPS ON/OFF personalisation 
Battery personalisation 
  
  Insert the Solution-Pac CD-ROM in the drive.
  On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal 
Solution-Pac software.
  Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of Personal Solution-Pac software do not offer this possibility.
It is possible to modify the settings listed below (detailed comments are available in the Personal Solution-Pac software).
Function
Factory setting
Other available settings
Output voltage 
 
 on battery power
230 Volts AC
200/208/220/240 Volts AC
Overload alarm threshold
105%
30/50/70%
Function
Factory setting
Other available settings
High threshold for transfer to battery
294 Volts AC
271 to 294 Volts AC
Low threshold for transfer to battery
160 Volts AC
160 to 180 Volts AC
Fader activation threshold
265 Volts AC
244 to 265 Volts AC
Booster activation threshold
184 Volts AC
184 to 207 Volts AC
Maximum input-voltage range
Disabled
Enabled 
(1)
Function
Factory setting
Other available settings
UPS-sensitivity level
Normal
High or low
Function
Factory setting
Other available settings
Automatic start
Enabled
Disabled
Cold start
Enabled
Disabled
Forced shutdown
Enabled
Disabled
Energy-savings mode
Disabled
Enabled
UPS ON/OFF controlled by software
Enabled
Disabled
Battery level before restart
0%
0 to 100%
Function
Factory setting
Other available settings
Battery-test intervals
Weekly
No test / daily test / monthly test
Low-battery warning
20%
0 to 100%
Battery protection against deep discharge
Enabled
Disabled
Audio alarm
Enabled
Disabled
Additional battery module (Evolution S models only)
Automatic detection of number 
of battery modules
For specific batteries, from 25 
to 81 Ah