IBM UPS 7500XHV User Manual

Page of 29
18
 
 6:  T
ROUBLESHOOTING
 
Use the chart below to solve minor uninterruptible power supply installation and operation problems. Refer to IBM for assis-
tance with complex uninterruptible power supply problems. 
P
ROBLEM AND 
P
OSSIBLE 
 
C
AUSE
 
S
OLUTION
 
UNINTERRUPTIBLE POWER SUPPLY WILL NOT TURN ON
 
The uninterruptible power 
supply is not connected to the 
utility power supply. 
Check that the power cord from the uninterruptible power supply to the util-
ity power supply is securely connected at both ends. 
The batteries are not con-
nected properly. 
Check that the battery connectors are fully engaged. 
There is very low or no utility 
voltage. 
Check the utility power supply to the uninterruptible power supply by plug-
ging in a table lamp. If the light is very dim, have the utility voltage 
checked. 
UNINTERRUPTIBLE POWER SUPPLY WILL NOT TURN OFF
 
There is an internal uninter-
ruptible power supply fault. 
Do not attempt to use the uninterruptible power supply. Unplug the uninter-
ruptible power supply and have it serviced immediately. 
UNINTERRUPTIBLE POWER SUPPLY BEEPS OCCASIONALLY
 
The uninterruptible power 
supply beeps when running on 
battery during normal opera-
tion. 
None. The uninterruptible power supply is protecting the connected equip-
ment from occasional utility power irregularities. 
UNINTERRUPTIBLE POWER SUPPLY IS NOT PROVIDING EXPECTED BACKUP TIME
 
The uninterruptible power 
supply battery is weak due to 
a recent outage or is near the 
end of its service life. 
Charge the battery. Batteries require recharging after extended outages, and 
wear faster when frequently put into service or when operated at elevated 
temperatures. If the battery is near the end of the service life, consider re-
placing the battery even if the replace battery LED is not yet lit. 
ALL LEDS ARE LIT AND THE UNINTERRUPTIBLE POWER SUPPLY EMITS A CONSTANT BEEPING
 
There is an internal uninter-
ruptible power supply fault. 
Do not attempt to use the uninterruptible power supply. Turn off the uninter-
ruptible power supply and have it serviced immediately. 
FRONT PANEL LEDS FLASH SEQUENTIALLY
 
The uninterruptible power 
supply has been shut down 
remotely through software. 
None. The uninterruptible power supply will restart automatically when 
utility power returns. 
ALL LEDS ARE OFF AND THE UNINTERRUPTIBLE POWER SUPPLY IS PLUGGED INTO A WALL OUTLET
 
The uninterruptible power 
supply is shut down or the 
battery is discharged from an 
extended outage. 
None. The uninterruptible power supply will return to normal operation 
when the power is restored and the battery has a sufficient charge.