IBM UPS1000THV User Manual

Page of 68
 
   
7
 
 
 2:  O
PERATION
 
 
Front Display Panel 
 
 
 
I
NDICATOR
 
D
ESCRIPTION 
 
Online 
 
This LED illuminates when the uninterruptible power supply is supplying utility power to 
the connected equipment. If not illuminated, the uninterruptible power supply is either not 
turned on, or is supplying battery power. When blinking, the uninterruptible power supply 
is running an internal self-test. 
AVR Trim 
 
This LED illuminates to indicate the uninterruptible power supply is compensating for a 
high utility voltage.  
AVR Boost 
 
This LED illuminates to indicate the uninterruptible power supply is compensating for a 
low utility voltage. 
On Battery  
 
This LED illuminates when the uninterruptible power supply is supplying battery power 
to the connected equipment.  
Overload 
 
This LED illuminates and the uninterruptible power supply emits a sustained alarm tone 
when the connected loads are drawing more than the uninterruptible power supply power 
rating (see Troubleshooting). 
Replace Battery/ 
Battery Disconnected 
 
Failure of a battery self-test causes the uninterruptible power supply to emit short beeps 
for one minute and this LED to illuminate (see Troubleshooting). 
This LED also flashes and a short beep is emitted every two seconds to indicate when the 
battery is disconnected (see Troubleshooting). 
F
EATURE
 
F
UNCTION
 
Power On 
 
Press this button to turn on the uninterruptible power supply. (Read on for additional ca-
pabilities.) 
Power Off 
 
Press this button to turn off the uninterruptible power supply. 
Self-Test  
Automatic: The uninterruptible power supply performs a self-test automatically when 
turned on, and every two weeks thereafter (by default). During the self-test, the uninter-
ruptible power supply briefly operates the connected equipment on battery. 
If the uninterruptible power supply fails the self-test, the replace battery LED illuminates 
and immediately returns to online operation. The connected equipment is not affected by a 
failed test. Allow the battery to recharge for 24 hours and perform another self-test. If it 
fails, the battery must be replaced. 
Manual: Press and hold the 
 button for a few seconds to initiate the self-test.