IBM UPS1000THV User Manual

Page of 68
 
   
 14
 
 
 
 6:  T
ROUBLESHOOTING
 
Use the chart below to solve minor uninterruptible power supply installation and operation problems. Refer to IBM for assis-
tance with complex uninterruptible power supply problems. 
P
ROBLEM AND
/
OR 
P
OSSIBLE 
 
C
AUSE
 
S
OLUTION
 
UNINTERRUPTIBLE POWER SUPPLY WILL NOT TURN ON
 
Uninterruptible power supply 
not connected to utility power 
supply. 
Check that the power cord from the uninterruptible power supply to the util-
ity power supply is securely connected at both ends. 
Battery not connected prop-
erly. 
Check that the battery connector is fully snapped into position. 
Very low or no utility voltage. 
Check the utility power supply to the uninterruptible power supply by plug-
ging in a table lamp. If the light is very dim, have the utility voltage 
checked. 
UNINTERRUPTIBLE POWER SUPPLY WILL NOT TURN OFF
 
Internal uninterruptible power 
supply fault. 
Do not attempt to use the uninterruptible power supply. Unplug the uninter-
ruptible power supply and have it serviced immediately. 
UNINTERRUPTIBLE POWER SUPPLY BEEPS OCCASIONALLY
 
Normal operating uninterrup-
tible power supply beeps 
when running on battery. 
None. The uninterruptible power supply is protecting the connected equip-
ment from occasional utility power irregularities. 
UNINTERRUPTIBLE POWER SUPPLY IS NOT PROVIDING EXPECTED BACKUP TIME
 
The uninterruptible power 
supply battery is weak due to 
a recent outage or is near the 
end of the service life. 
Charge the battery. Batteries require recharging after extended outages, and 
wear faster when frequently put into service or when operated at elevated 
temperatures. If the battery is near the end of the service life, consider re-
placing the battery even if the replace battery LED is not yet illuminated. 
ALL LEDS ARE ILLUMINATED AND THE UNINTERRUPTIBLE POWER SUPPLY EMITS A CONSTANT 
BEEPING
 
Internal uninterruptible power 
supply fault. 
Do not attempt to use the uninterruptible power supply. Turn off the uninter-
ruptible power supply and have it serviced immediately. 
FRONT PANEL LEDS FLASH SEQUENTIALLY
 
The uninterruptible power 
supply has been shut down 
remotely through software or 
an optional accessory card. 
None. The uninterruptible power supply will restart automatically when 
utility power returns. 
ALL LEDS ARE OFF AND THE UNINTERRUPTIBLE POWER SUPPLY IS PLUGGED INTO A WALL OUTLET
 
The uninterruptible power 
supply is shut down or the 
battery is discharged from an 
extended outage. 
None. The uninterruptible power supply will return to normal operation 
when the power is restored and the battery has a sufficient charge. 
THE OVERLOAD LED IS ILLUMINATED AND THE UNINTERRUPTIBLE POWER SUPPLY EMITS A SUS-
TAINED ALARM TONE
 
The uninterruptible power sup-
ply is overloaded. The con-
nected equipment is drawing 
more VA or more Watts than 
the uninterruptible power sup-
ply can sustain. 
The connected equipment exceeds the specified “maximum load.” 
The alarm remains on until the overload is removed. Disconnect nonessen-
tial equipment from the uninterruptible power supply to eliminate the over-
load. 
The uninterruptible power supply continues to supply power as long as it is 
online and the circuit breaker does not trip; the uninterruptible power sup-
ply will not provide power from batteries in the event of a utility voltage 
interruption. 
If a continuous overload occurs while the uninterruptible power supply is 
on battery, the unit turns off output in order to protect the uninterruptible 
power supply from possible damage.