IBM UPS1500THV User Manual

Page of 68
 
   
15
 
 
P
ROBLEM AND
/
OR 
P
OSSIBLE 
 
C
AUSE
 
S
OLUTION
 
THE REPLACE BATTERY LED IS ILLUMINATED
 
Replace battery LED flashes 
and short beep is emitted every 
two seconds to indicate the 
battery is disconnected. 
Check that the battery connectors are fully engaged. 
Weak battery. 
Allow the battery to recharge for 24 hours. Then, perform a self-test. If the 
problem persists after recharging, replace the battery. 
Failure of a battery self-test. 
The uninterruptible power supply emits short beeps for one minute and the 
replace battery LED illuminates. The uninterruptible power supply repeats 
the alarm every five hours. Perform the self-test procedure after the battery 
has charged for 24 hours to confirm the replace battery condition. The 
alarm stops and the LED clears if the battery passes the self-test. 
THE SITE WIRING FAULT LED ON THE REAR PANEL IS ILLUMINATED 
(750TLV, 1000TLV & 1500TLV 
MODELS
 
ONLY
)
 
The uninterruptible power sup-
ply is plugged into an improp-
erly wired utility power outlet. 
Wiring faults detected include missing ground, hot-neutral polarity reversal, 
and overloaded neutral circuit.  
Contact a qualified electrician to correct the building wiring. 
THE INPUT CIRCUIT BREAKER HAS TRIPPED
 
The plunger on the circuit 
breaker pops out. 
Reduce the load on the uninterruptible power supply by unplugging equip-
ment. Press in the plunger on the circuit breaker. 
THE AVR BOOST OR TRIM LEDS ARE ILLUMINATED
 
Your system is experiencing 
excessive periods of low or 
high voltage. 
Have qualified service personnel check your facility for electrical prob-
lems. If the problem continues, contact the utility company for further as-
sistance. 
UNINTERRUPTIBLE POWER SUPPLY OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE 
EXISTS
 
The uninterruptible power 
supply input circuit breaker 
tripped.  
To reduce the load on the uninterruptible power supply, unplug equipment 
and press in the plunger on the circuit breaker.  
Very high, low, or distorted 
line voltage.  
Move the uninterruptible power supply to a different outlet on a different 
circuit, as inexpensive fuel powered generators may distort the voltage. Test 
the input voltage with the utility voltage display (see Operation). If accept-
able to the connected equipment, reduce the uninterruptible power supply 
sensitivity.  
BATTERY CHARGE AND BATTERY LOAD LEDS FLASH SIMULTANEOUSLY
 
The uninterruptible power 
supply has shutdown. The 
internal temperature of the 
uninterruptible power supply 
has exceeded the allowable 
threshold for safe operation. 
Check that the room temperature is within the specified limits for operation. 
Check that the uninterruptible power supply is properly installed, allowing 
for adequate ventilation. 
Allow the uninterruptible power supply to cool down. Restart the uninter-
ruptible power supply. If the problem continues, contact IBM.