Liebert UPS User Manual
35
SPECIFICATIONS
MODEL NUMBER
GXT6000T-240X
GXT10000T-240X
MODEL RATING VA/W (max)
6000 / 4200
10000 / 7000
DIMENSIONS: mm (in)
Unit
W x D x H
260 x 555 x 803
(10.3 x 21.9 x 31.6)
340 x 650 x 960
(13.4 x 25.6 x 37.8)
Shipping
W x D x H
400 x 850 x 1065
(15.8 x 33.5 x 41.9)
510 x 840 x 1235
(20.1 x 33.1 x 48.6)
WEIGHT: kg (lbs)
Unit
139 (306)
244 (538)
Shipping
170 (374)
284 (626)
INPUT AC PARAMETERS
Voltage Range (typical)
240 VAC nominal; variable based upon output load
100% - 90% Loading
186 VAC to 280 VAC; ±5.0 VAC
90% - 70% Loading
159 VAC to 280 VAC; ±5.0 VAC
70% - 30% Loading
139 VAC to 280 VAC; ±5.0 VAC
30% - 0% Loading
119 VAC to 280 VAC; ±5.0 VAC
Frequency
46.6 – 52.4 Hz or 57.1 - 62.9 Hz; auto sensing
Input connection
Hardwire terminal block
OUTPUT AC PARAMETERS
Output connection
Hardwire terminal block
Voltage
208/104, 220/110, 230/115,240/120 VAC (switch
selectable); ±7%
Frequency
50 Hz or 60 Hz; auto sensing
Waveform
Sinewave
Main Mode Overload
200% for 8 cycles; 130% for 10 seconds, then transfer to
bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Qty. x Voltage x Rating
20 x 12V x 7.0 Ah
40 x 12V x 7.0 Ah
Back-up Time
7 min. minimum
10 min. minimum
ENVIRONMENTAL
Operating Temperature
0° C to +40° C (+32° F to +104° F)
Storage Temperature
-15° C to +50° C (+5° F to +122 °F)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 3000 m (10,000 ft.) at 40° C without derating
Storage Elevation
15,000 m (50,000 ft.) maximum
Audible Noise
<55 dB ”A” at 1 meter
<65 dB ”A” at 1 meter
AGENCY
Safety
UL 1778; Listed
EMI/EMC
FCC Part 15 Class A
Immunity
IEEE C62.41:199