Liebert UPS User Manual

Page of 37
 
35
SPECIFICATIONS 
MODEL NUMBER 
GXT6000T-240X 
GXT10000T-240X 
MODEL RATING VA/W (max) 
6000 / 4200 
10000 / 7000 
DIMENSIONS: mm (in) 
Unit 
W x D x H 
260 x 555 x 803 
(10.3 x 21.9 x 31.6) 
340 x 650 x 960 
(13.4 x 25.6 x 37.8) 
Shipping 
W x D x H 
400 x 850 x 1065 
(15.8 x 33.5 x  41.9) 
510 x 840 x 1235 
(20.1 x 33.1 x  48.6) 
WEIGHT: kg (lbs) 
Unit 
139 (306) 
244 (538) 
Shipping 
170 (374) 
284 (626) 
INPUT AC PARAMETERS 
Voltage Range (typical) 
240 VAC nominal; variable based upon output load 
100% - 90% Loading 
186 VAC to 280 VAC; ±5.0 VAC 
90% - 70% Loading 
159 VAC to 280 VAC; ±5.0 VAC 
70% - 30% Loading 
139 VAC to 280 VAC; ±5.0 VAC 
30% - 0% Loading 
119 VAC to 280 VAC; ±5.0 VAC 
Frequency 
46.6 – 52.4 Hz or 57.1 - 62.9 Hz; auto sensing 
Input connection 
Hardwire terminal block 
OUTPUT AC PARAMETERS 
Output connection 
Hardwire terminal block 
Voltage 
208/104, 220/110, 230/115,240/120 VAC (switch 
selectable); ±7% 
Frequency 
50 Hz or 60 Hz; auto sensing 
Waveform 
Sinewave 
Main Mode Overload 
200% for 8 cycles; 130% for 10 seconds, then transfer to 
bypass 
BATTERY PARAMETERS 
Type 
Valve-regulated, nonspillable, lead acid 
Qty. x Voltage x Rating 
20 x 12V x 7.0 Ah 
40 x 12V x 7.0 Ah 
Back-up Time 
7 min. minimum 
10 min. minimum 
ENVIRONMENTAL 
Operating Temperature 
0° C to +40° C (+32° F to +104° F) 
Storage Temperature 
-15° C to +50° C (+5° F to +122 °F) 
Relative Humidity 
0% to 95%, non-condensing 
Operating Elevation 
Up to 3000 m (10,000 ft.) at 40° C without derating 
Storage Elevation 
15,000 m (50,000 ft.) maximum 
Audible Noise 
<55 dB ”A” at 1 meter 
<65 dB ”A” at 1 meter 
AGENCY 
Safety 
UL 1778; Listed  
EMI/EMC 
FCC Part 15 Class A 
Immunity 
IEEE C62.41:199