Chapter 10  Service after Sales 
115 
No.1 
Fault description 
Reason 
Actions to be taken 
34 Output 
surge 
current 
Surge current occurs in bypass 
mode, the system shutdown 
Avoid applying big load abruptly and 
short circuit 
35 
Transfer to bypass due to 
surge 
The system transfers to bypass 
mode due to surge current and 
back to inverter mode after load is 
decreased 
Avoid applying load abruptly and the 
UPS can recover automatically 
36 
Neighbouring UPS module 
requires to transfer to 
bypass mode 
In parallel operation system, 
some UPS module may require to 
transfer to bypass due to surge or 
overload, other modules will 
transfer to bypass after receiving 
the signal sent by this UPS 
module that requires to transfer to 
bypass mode 
If the parallel operation system 
transfers to bypass mode, and the 
operation condition enables, all the 
UPS modules can recover to normal 
mode synchronously. 
37 User’s 
wrong 
operation 
Wrong operation such as start the 
UPS with the maintenance 
bypass switched on 
Operate with reference to User’s 
Manual 
38 
The actual transfer times 
exceed the permissible 
transfer  times per hour  
Transfer times exceed the times 
set by background. The system 
will stay in bypass mode until next 
hour. 
Avoid frequent overload 
 
10.2  Warranty 
We provide 1 year of free service for our UPS (including the battery). 
The above warranty shall not apply in the following circumstances: 
The battery is provided by user; 
Damage resulting from operation not in accordance with the user manual; 
Damage as a result of fire, flood, etc.; 
Different levels of customized service packages are available with reasonable 
charge, including responsive, preventive maintenance, warranty period extension, 
etc. For detailed information, please contact the distributor or the local technical 
support center.