Liebert 1500 User Manual

Page of 59
Specifications          11
Figure 10 Front view of the (4) CRS200P 150-200 A/(4) CRS200P 150-200 A (w/load shunts) fuse panels
The DC output connections are 0.50-13 studs equipped with two hex nuts.
Figure 11 Front view of the (4) TPL 225-600 A fuse panels
The DC output connections are busbar angles that can accept 535MCM or 750MCM cables, or the 
metric equivalent. The lugs must be for two 1/2” dia. bolts at 1-3/4” c-c.
Table 12
Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150-200 A (w/load 
shunts) fuse panels
Fuse type
Current (A)
CPC
HRC1-J
110
A0329697
125
A0329696
150
A0722041
175
A0722038
200
A0614832
Table 13
Fuse sizes available for the (4) TPL 225-600 A fuse panels
Fuse type
Current (A)
CPC
DC power (TPL)
225
A0380138
300
A0380140
400
A0380141
500
A0380142
600
A0380143
FA
(2)
(3)
(4)
(1)
ALM
(2)
(3)
(4)
(1)
ALM
FA
ALM
(2)
(3)
(4)
(1)
ALM
(2)
(3)
(4)
(1)
-48 V